摘要 以1座光伏电站接入系统后,在其电力送出网络中第一落点变电站2台主变压器中1台发生故障时存在的过载问题为例,进行了N-1故障校验分析。提出采用在电网相关厂(站)装设安全自动装置的措施,并给出具体装置配置方案及控制策略,以解决地区电网在新能源电力接入系统后N-1故障情况下的主变压器过载问题。 Based on the intergration of a photovoltaic power station which facing theproblem of transformer overload when either of the two transformers in access substationbreaks down, make an analysis of N-1 fault checking. Then proposes the mearsure whichinstalls automatic safety devices in related stations and gives out specific configurationscheme of device and control strategies, which can solve the problem of transformeroverload under N-1 principle caused by renewable energy′s access grid effectively.
作者 马维旺 冯欢
出处 《内蒙古电力技术》 2015年第6期11-14,共4页 Inner Mongolia Electric Power
关键词 新能源 光伏电站 N-1故障 过载 安全自动装置 new energy photovoltaic power station N-1 faults overload automaticsafety device
  • 相关文献

参考文献7

  • 1电力行业电网运行与控制标准化技术委员会.DL755-2001电力系统安全稳定导则[S].北京:中国电力出版社,2001.
  • 2中国电力科学研究院.PSD-BPA潮流程序用户手册(4.0版)[R].北京:中国电力科学研究院,2007:5.
  • 3[日]太阳能光伏发电协会浏树民,宏伟,译.太阳能光伏发电系统的设计与施工[M].北京:科学出版社,2006:105-111.
  • 4白云,朱昱.光伏电站接入系统方案研究[J].广东电力,2012,25(3):68-71. 被引量:6
  • 5内蒙古电力(集团)有限责任公司.PG003--2015内蒙古电力(集团)有限责任公司光伏发电站接人电网技术规定[R].呼和浩特:内蒙古电力(集团)有限责任公司,2015.
  • 6中国电力企业联合会.GB/T19964--2012光伏发电站接人电力系统技术规定[S].北京:中国标准出版社,2013.
  • 7电力行业电力规划设计标准化技术委员会.DL/T5147—2001电力系统安全自动装置设计技术规定[s].北京:中国电力出版社,2002.