10kV配电网中中性点接地电阻柜保护误动原因分析与解决措施 被引量:3

False Protection Analysis of Neutral Point Grounding ResistanceCabinet in 10 kV Distribution Network and Its Treatment
下载PDF
导出
摘要 中性点接地电阻柜的应用实现了10 kV配电网零序电流保护配置及故障跳闸,但由于应用技术不成熟,易造成保护误动事故。针对鄂尔多斯电网所辖110 k V降压变电站中性点接地电阻柜在运行时发生的多次保护误动情况,分析认为主要原因是零序TA测量存在误差、电缆屏蔽层接地线走向不正确、10 k V馈线开关保护误动等,并制订相应的解决措施,从而实现了中性点接地电阻柜在10 kV配电网中的有效应用。 The application of neutral point grounding resistance cabinet can realize thezero sequence current protection configuration of 10 k V distribution network and fault trip,but due to the application of immature technology, it could easily lead to protectionmalfunction accident. Through the analysis of the multiple protection malfunction occurredduring the operation of the 110 k V substation neutral grounding resistor cabinet withinOrdos grid, the main causes are the error of the zero sequence TA measurement, the errorof the cable shield to the ground wire and the error of the 10 k V feeder switch protectionmalfunction, etc., and formulate the corresponding solution measures, so as to achieve theeffective application and management of neutral point grounding resistance cabinet in 10 kV distribution network.
作者 王亮
机构地区 鄂尔多斯电业局
出处 《内蒙古电力技术》 2015年第6期79-81,85,共4页 Inner Mongolia Electric Power
关键词 10kV配电网 中性点接地电阻柜 零序电流保护 零序TA 10kV馈线开关 电缆屏蔽层接地线 10 kV distribution network neutral point grounding resistance cabinet zerosequence current protection zero sequence TA 10 k V feeder switch cable shield groundwire