期刊文献+

基于下垂特性的开关信号及接收相位双同步组网控制 被引量:3

Integration Control Based on Droop Characteristics Achieving Double Synchronization with the Switching Signal and the Reception Phase
下载PDF
导出
摘要 针对静止式中频电源组网系统的难点,在理论分析中频组网系统下垂控制的基础上,对传统无互联线下垂控制加以改进。在考虑组网连线阻抗影响、非线性负载影响及组网单元相位同步的基础上,提出了基于下垂特性的开关信号及接收相位双同步组网控制策略,该方法通过引入带高通滤波器的虚拟阻抗对输出阻抗进行设计,消除了连线阻抗及非线性负载对均流效果的影响;同时,组网单元通过CAN总线共享同步相位,采用固有延时补偿实现开关信号的同步,并对接收相位进行实时及过零点补偿,消除延时影响和过零点电压畸变,实验结果中输出电压总谐波含量为2.28%,环流峰值小于5 A,证明了该控制算法良好的环流抑制效果。 To solve the difficulties in the 400 Hz solid-state power supply integration system, the traditional droop control was improved. In consideration of connection impedance effects, nonlinear load effects and integration unit phase syn- chronization, a novel strategy of integration control was proposed based on droop characteristics to achieve double synchronization with the switching signal and the reception phase. In this control, the output impedance was designed by a virtual impendence with the high pass filter, which could eliminate the current sharing effects of connection impedance and nonlinear load. Besides, the integration units shared the sync phase by CAN bus and synchronize switching signal by inherent time delay compensation. The compensation for the reception phase could eliminate the time delay effect and the zero crossing voltage distortion. The total harmonic distortion of output voltage was 2.28% and the magnitude of circula- tion was less than 5 A, which proved that the integration control had a good circulation inhibitory effect.
出处 《高电压技术》 EI CAS CSCD 北大核心 2016年第1期303-314,共12页 High Voltage Engineering
基金 国家自然科学基金(51407189)~~
关键词 静止式中频电源 组网系统 下垂控制 虚拟阻抗 双同步组网控制 补偿 400 Hz solid-state power supply integration system droop control virtual impendence double synchroni-zation integration control compensation
  • 相关文献

参考文献15

二级参考文献183

共引文献278

同被引文献29

引证文献3

二级引证文献28

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部