摘要
介绍了发电厂起备变冷备用运行方式下厂用电切换的过程及控制原理,对影响起备变冷备用运行的变压器空投时差动保护误动作、母线失压时间增加导致快切失败、冷备用时设备带故障投入、对电压跌落敏感的厂用负荷跳闸等问题进行分析,结合实例介绍了起备变冷备用技术的应用情况,并对采用此运行方式导致的厂用电切换失败后果进行了分析,指出该技术的可行性。
For standby transformer working as cold reserve, this paper is not only focus on the operation process and basic principle of its service power switching, but also try to work out the problems which influenced its normal work. So it analyzed the reason of differential protection malfunction when transformer input with no-load and discussed the failure action of fast switching device under the long time voltage-losing inbus. Besides, the troubles like cold reserve put into system with fault and the switches tripping by some sensitive devices when the bus voltage dropped down had also been talked here. After the consideration of real situation in power plant and the judgments for problems above, this paper made an assessment of feasibility if the standby transformer could working as a cold reserve in power plant.
出处
《电气技术》
2015年第12期131-134,138,共5页
Electrical Engineering
基金
华能国际660MW高效超超临界燃煤机组应用技术研究--材料和调试专题研究
关键词
起备变
冷备用
快切
励磁涌流
standby transformer
cold reserve
fast switching device
inrush current