摘要
阐述了智能变电站电流互感器的正极性接法与反极性接法;讨论智能变电站常规互感器加合并单元接线形式的二次回路原理;通过对比常规变电站和智能变电站电流互感器的典型配置,分别描述线路保护、母线保护以及变压器保护原理,并解释当电流互感器的电流同时供给两个保护装置时,电流互感器的极性如何配置。
This paper elaborated methods of both positive wiring and the negative wiring of current transformers (CTs) in smart substation ; discussed the principle of the secondary circuit according to the connection form of ' Cir- cuit Transformer + Merging Unit' in digitized substation. By comparing the typical structures of conventional substa- tion and smart substation, the principles of transmission line protection, bus bar protection and power transformer pro- tection were described respectively. It is significant to how to apply the polar wiring of CTs when one CT supplies current for two protection devices.
出处
《华北电力技术》
CAS
2016年第2期27-32,共6页
North China Electric Power
关键词
智能变电站
电流互感器
正极性接法
反极性接法
合并单元
线路保护
母线保护
变压器保护
smart substation, current transformer, merging unit, method of positive wiring, method of negative wiring,line protection, bus-bar protection, transformer protection