期刊文献+

热老化对变压器绝缘纸微观结构影响的实验研究 被引量:15

Experimental Research on Thermal Aging Effects on Microstructure of Transformer Paper
下载PDF
导出
摘要 为了研究热老化应力对变压器绝缘纸微观结构的影响,以更准确地分析油纸绝缘机械强度和绝缘性能,文中对油浸纸试品进行加速热老化实验,获取不同老化程度的变压器绝缘纸试样。测量了绝缘纸试样的聚合度,采用扫描电镜观察绝缘纸试样的表面微观形貌,通过傅里叶变换红外光谱(FTIR)分析纤维素分子结构变化。分析结果表明,热老化对变压器绝缘纸微观纤维结构破坏显著,纤维细化,断裂增多,纤维分子结构及相关官能团数量变化明显。 To investigate thermal aging stress effects on microstructure of transformer paper for more accurate analysis of mechanical strength and insulation performance of oil-paper insulation,the accelerated thermal aging experiment is performed on oil-paper samples in this work and some samples of different aged states are obtained. The surface micro-topography of paper samples is observed by Scanning Electron Microscope(SEM)and the changes of molecular structure are analyzed by Fourier Transform Infrared Spectroscopy(FTIR).Experimental results show that thermal aging stress brings significant changes to microstructure of paper fiber.The cellulose fiber becomes thinner and shorter. In addition, the molecular structure of cellulose fiber and the quantity of some function groups change obviously.
出处 《高压电器》 CAS CSCD 北大核心 2016年第2期93-96,102,共5页 High Voltage Apparatus
关键词 热老化 绝缘纸 微观形貌 SEM FTIR thermal aging insulation paper micro-topography SEM FTIR
  • 相关文献

参考文献17

  • 1中国人民共和国国家发展和改革委员会.DL/T1094—2008电力变压器用绝缘油选用指南[S].北京:中国电力出版社.2008.
  • 2EMSLEY A M,STEVENS G C. Kinetics and mechanisms of the low-temperature degradation of cellulose[J]. Cellulose, 1994,1(1) :26-56.
  • 3HILL D,LE T T,DARVENIZA M,et al. A study of the degradation of cellulosic insulation materials in a power transformer 3:Degradation products of cellulose insulation paper[J]. Polymer Degradation and Stability, 1996,51 (2): 211-218.
  • 4刘玉仙.油纸绝缘变压器中水分的聚积及其对热老化寿命的影响[J].变压器,2004,41(2):8-13. 被引量:68
  • 5朱晓伟,梁榕珊.温度对油纸绝缘结构的击穿特性影响的研究[J].电力电容器与无功补偿,2014,35(1):64-68. 被引量:9
  • 6HILL D J, LET T, DARVENIZA M, et al. A study of degra- dation of cellulosic insulation materials in a power trans- former 2:Tensile-strength of cellulose insulation paper[J]. Polymer Degradation and Stability, 1995,49(3) : 429-435.
  • 7HILL D, LE T T, DARVENIZA M, et al. A study of degra- dation of cellulosic insulation materials in a power trans- former 1 : Molecular-weight study of cellulose insulation pa- per[J]. Polymer Degradation and Stability, 1995,48(1) :79-87.
  • 8HOHLEIN I, KACHLER A J. Aging of cellulose at trans- former service temperatures. Part 2:Influence of moisture and temperature on degree of polymerization and formation of furanic compounds in free-breathing systems[J]. IEEE Electrical Insulation Magazine, 2005,21 (5) :20-24.
  • 9KACHLER A J, HOHLEIN I. Aging of cellulose at trans- former service temperatures. Part 1 : Influence flu of type of oil and air on the degree of polymerization of pressboard, dissolved gases, and furanic compounds in oil[J]. IEEE Electrical Insulation Magazine,2005,21(2): 15-21.
  • 10LUNDGAARD L E,HANSEN W,LINHJELL D,et al. Ag- ing of oil-impregnated paper in power transformers[J]. IEEE Transactions on Power Delivery, 2004,19(1) : 230-239.