期刊文献+

电缆接头温度反演及故障诊断研究 被引量:38

Research on Temperature Retrieval and Fault Diagnosis of Cable Joint
下载PDF
导出
摘要 为间接测量得到电缆导芯温度、预防电缆接头故障,建立了电缆接头2阶和1阶暂态热路简化模型,提出了一种电缆接头导芯温度的反演算法,推导得出导体实时温度。同时,通过参数辨识对电缆接头进行在线监测并得到故障诊断结果。结果表明,建立的电缆接头2阶和1阶暂态热路模型可有效简化反演计算,进而通过电缆接头外皮和金属护套温度反推出导体温度,且所得反演结果与实测结果相符。此外,根据辨识参数相对正常运行状态时的变化情况,可判断出电缆接头是否存在故障隐患以及是何种故障。 To obtain the cable joint core temperature indirectly and prevent the fault of cable joint, we established the second- and first-order transient thermal circuit simplified models of cable joint, and proposed a retrieval algorithm to calculate the conductor temperature of cable joint; and then the conductor real-time temperature could be deduced. Meanwhile, the fault diagnosis results of cable joint could be obtained by online monitoring cable joints by using para- meter identification. The results show that the proposed first- and second-order model for transient thermal circuit inversion calculation can simplify the inversion computation; the conductor temperature derived from the temperatures of cable joint surface and metal sheath is consistent with the conductor temperature detected in actual measurement. Mean- while, it is also possible to determine whether fault risks will occur and which types of faults will "occur according to the variation Of identification parameter in relatively normal state.
出处 《高电压技术》 EI CAS CSCD 北大核心 2016年第2期535-542,共8页 High Voltage Engineering
基金 国家自然科学基金(51307127)~~
关键词 电缆接头 电缆导体温度 最小二乘法 在线监测 温度反演 故障诊断 cable joint temperature of cable conductor LSM online monitoring temperature retrieval fault diagnosis
  • 相关文献

参考文献21

二级参考文献288

共引文献842

同被引文献425

引证文献38

二级引证文献233

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部