选厂鼓风机温度开关误动作改进措施

Improvement Measure on Temperature Switch of Blower in Processing Plant
下载PDF
导出
摘要 鼓风机在选矿厂中具有重要作用,为其浮选机选矿作业提供稳定、充足的风量。以D-850鼓风机控制系统为实例,针对鼓风机因温度开关误动作,造成跳闸次数多,提出鼓风机控制系统改造的可行性方案。通过改变测量信号线连接方式、温度波动增加延时动作、重新接过信号线与屏蔽线,组织实施后,有效降低了风机故障频次、改善设备运行状况。 Blower is an important role in processing plant, it provides stable, adequate air for flow flotation machine in processing operations. Using D-850 blower control system as an example, since the malfunction of temperature switch caused the trip more often, a feasibility program of blower control system is proposed. By changing the measurement signal-wire connection, temperature fluctuations increased delay action, re-took the signal line and shielded wire, after the effective organization and implement, the fan failure frequency is reduced and equipment operation is improved.
作者 黎婷 王显盛
出处 《铜业工程》 CAS 2016年第1期80-83,共4页 Copper Engineering
关键词 鼓风机 跳闸 温度开关 接线 误动作 改进措施 blower trip temperature switch wiring malfunction improvement measures