期刊文献+

主变压器冷却器油渗漏治理方案

Treatment Schemes of Oil Leakage for Main Transformer Cooler
下载PDF
导出
摘要 对邹县发电厂三期主变压器冷却器连接短管的连接结构、楔形密封结构进行研究,确认连接短管的密封圈老化,密封失效是短管渗漏油的主要因素。利用不锈钢波纹管的良好可挠性和伸缩性,以及耐温、耐压、耐腐蚀特点,将连接短管更换为不锈钢波纹管,采用新的设计方案,减少渗漏点,保证设备的可靠运行。 By studying the structure of eonneeting short pipe and sealing wedge for the main transformer cooler of the third phase project in Zouxian power plant, it is confirmed that the main factor of oil leakage is the aging of sealing ring. Because of the fact that the stainless steel bellow is flexible and its characteristics of heat resistance, good compression, being anti- corrnsive, stainless steel bellow has been used as the connectiug short pipe. New design scheme is adopted, oil leakage points are reduced and reliable operation of equipment is ensured.
出处 《山东电力技术》 2016年第1期59-61,共3页 Shandong Electric Power
关键词 主变压器 冷却器 连接短管 油渗漏 不锈钢波纹管 main transformer cooler connecting short pipe oil leakage stainless steel bellows
  • 相关文献

参考文献2

二级参考文献2

  • 1.变压器故障诊断与修理[M].机械工业出版社,1 998..
  • 2.电力变压器检修与实验手册[M].中国电力出版社,2000..

共引文献14