摘要
通过理论推导,分析储存体积相同、管道进口压力相同和变化两种情况下,两种不可压缩流体不稳定流动的时间比,证明水和不可压缩流气体灭火剂喷射时间的相似性,获取了水替代不可压缩流气体灭火剂喷射时间的定量修正参数。以七氟丙烷和水为例进行了实际喷射对比实验,进一步验证了理论推导的修正参数的准确性。
By theoretical deduction, the time proportion of two kinds of incompressible fluid under the situation of same storage volume, same and different pipe input pressure was analyzed, to prove the similarity of the discharge time between water and incompressible gas extinguishant, and got the correction param- eters of the discharge time of water replacing incompressible gas extinguishant. A contrast experiment research was made be- tween the water and Heptafluoropropane, which further veri- fied the accuracy of correction parameters.
出处
《消防科学与技术》
CAS
北大核心
2016年第3期376-379,393,共5页
Fire Science and Technology
基金
公安部天津消防研究所科研计划项目"水替代液态气体灭火剂喷放修正参数的理论与实验研究"(2016SJ-A-39)
关键词
不可压缩流体
灭火剂
七氟丙烷
喷射时间
incompressible fluid
extinguishing fluid
Heptaflu-oropropane
discharge time