摘要
为了满足保证系统电压稳定、降低高压电网网损的现实要求,系统分析了电压调整的基本原理,经比较后选取晶闸管控制电抗器(TCR)动态无功补偿调压方案。详细地阐述了无功补偿和电压调整过程,特别是引入了最小均方(LMS)自适应滤波算法对基本控制方法进行了改进,此改进方法可提高控制精度,加快收敛速度。还以500 kV超高压300 km长距离输电线路为例,在Matlab中搭建了12脉波接法的TCR调压模型,无功补偿以及调压的效果都验证了TCR作为调压措施的快速性和动态性。
In order to ensure the voltage stability of system and reduce the high-voltage network loss, improve power quality, a scheme of compensating reactive power is proposed in this paper. Firstly, the basic principle of voltage reg- ulation is introduced. After making comparison with several control methods, thyristor controlled reactor (TCR) com- pensator is selected due to its certain feasibility and stability. Besides, the reactive power compensation and voltage regulation process are elaborated in detail, and the improving control strategy is performed based on the least mean square (LMS) algorithm, which makes it vital in accelerating convergence rate and enhancing control accuracy. At last, a 500 kV extra high voltage and 300 km long-distance transmission line model are built with 12-pulse connection structure of TCR. The Matlab simulation results verify the theoretical analysis and provide with super advantages in ac- celerating dynamic response.
出处
《电测与仪表》
北大核心
2016年第4期5-13,共9页
Electrical Measurement & Instrumentation
基金
国家自然科学基金资助项目(61304134)
上海市重点科技攻关计划(14110500700)
上海市电站自动化技术重点实验室(13DZ2273800)
关键词
电压调整
无功补偿
LMS算法
12脉波TCR
voltage regulation, reactive power compensation, LMS algorithm, 12-pulse connection TCR