期刊文献+

不同气象条件下地铁屏蔽门系统能耗分析 被引量:1

Energy Consumption of Subway Platform Screen Door Under Different Meteorological Conditions
下载PDF
导出
摘要 为了分析屏蔽门系统在不同气象参数条件下的节能效果,利用STESS软件对温带季风气候、亚热带季风气候和热带季风气候条件下安装屏蔽门系统前后地铁能耗变化情况进行了模拟研究。通过对有无屏蔽门系统条件的地铁环控能耗模拟,得到各个地区屏蔽门系统环控节能百分比,结果显示:温带季风气候条件下安装屏蔽门系统初期节能约0.51%,近期增加能耗约11.5%,远期增加能耗约20.0%;亚热带季风气候条件下屏蔽门系统初期节能约15.7%,近期节能约12.2%,远期节能约6.9%;热带季风气候条件下屏蔽门系统初期节约22.8%,近期节能约22.4%,远期节能约19.9%。 To analyze the energy saving effect of subway platform screen door under different meteorological conditions, the software of STESS was used to simulate the change of energy consumption which was before and after the installation of platform screen door about temperate monsoon climate,subtropical monsoon climate and tropical monsoon climate. Energy-saving percentage of platform screen door was obtained by energy consumption analysis which is under the condition with the platform screen door and without the platform screen door. Results showed:under the condition of temperate monsoon climate, energy saving of the platform screen door was about 0.51% in the early time, the energy consumption increased about 11.5% in the recent time and increased about 20.0% in the remote time;under the condition of subtropical monsoon climate, energy saving of the platform screen door was about15.7% in the early time, 12.2% in the recent time and 6.9% in the remote time; under the condition of tropical monsoon climate, energy saving of the platform screen door was about 22.8% in the early time,22.4% in the recent time and 19.9% in the remote time. The conclusion provides theory basis to research the weather platform screen door system is reasonable or not under different meteorological conditions.
出处 《建筑节能》 CAS 2016年第3期110-114,共5页 BUILDING ENERGY EFFICIENCY
关键词 屏蔽门系统 气候 能耗模拟 节能 STESS platform screen door meteorological conditions energy consumption simulation energy saving STESS
  • 相关文献

参考文献6

  • 1Yoshiharu Soeta,Ryota Shimokura.Change of acoustic characteristics caused by platform screen doors in train stations[J].Applied Acoustics,2012,73(5):535-542.
  • 2Ki-Hyum Kim,Duy Xuan Ho,Jae-Sik Jeon,et al.A noticeable shift in particulate matter levels after platform screen door installation in a Korean subway station[J].Atmospheric Environment,2012,49:219-223.
  • 3X.Querol,T.Moreno,A.Karanasiou,et al.Variability of levels and composition of PM10 and PM2.5 in the Barcelona metro system[J].Atmos.Chem.Phys.,2012,(12):5055-5076.
  • 4Son Y S,Jeon J S,Lee H J,et al.Installation of platform screen doors and their impact on indoor air quality:Seoul subway trains[J].J Air Waste Manaq Assoc.,2014,64(9):1054-1061.
  • 5Wonhwa Hong,Samuel Kim.A study on the energy consumption unit of subway stations in Korea[J].Building and Environment,2004,39(12):1497-1503.
  • 6曹荣光,由世俊,董书芸.北方地铁屏蔽门系统能耗分析及节能改造[J].重庆大学学报(自然科学版),2009,32(2):218-222. 被引量:7

二级参考文献13

  • 1郑晋丽.通风如何控制地铁区间隧道温度[J].地下工程与隧道,1996(1):40-42. 被引量:2
  • 2吴培浩,杨仕超,马扬,张士翔.地铁屏蔽门风压实测研究[J].城市轨道交通研究,2007,10(6):57-59. 被引量:17
  • 3AMPOFO F, MAIDMENT G, MISSENDEN J. Underground railway environment in the UK part 2: investigation of heat load [J]. Applied Thermal Engineering, 2004,24 (4) : 633-645.
  • 4HU S C, LEE J H. Influence of platform screen doors on energy consumption of the environment control system of a mass rapid transit system: case study of the Taipei MRT system[J]. Energy Conversion and Management, 2004,45 (5):639-650.
  • 5MOIN P, KIM J. Numerical investigations of turbulent channel flow[J]. Fluid Mechanics, 1982,118:341-377.
  • 6KE M T, CHENG T C, WANG W P. Numerical simulation for optimizing the design of subway environmental control system[J]. Building and Environment, 2002,37 (8) : 1139-1152.
  • 7ZHANG L, FENG J, CHOW T T, et al. CFD analysis of ventilation effectiveness in a public transport interchange[J]. Building and Environment, 2006,41(3) :254-261
  • 8KAZUHIRO F. Application of computational fluid dynamics and pedestrian-behavior simulations to the design of task-ambient air-conditioning systems of a subway station[J]. Energy, 2006, 31(7):706-718.
  • 9HONG W W, KIM S. A study on the energy consumption unit of subway stations in Korea [J]. Building and Environment, 2004, 39(12):1497-1503.
  • 10DRURY B C, HAND J W. Improving the weather information available to simulation programs[J]. In Proceedings of Building Simulation, 1999(2):529-536.