期刊文献+

超超临界直流机组吹管期间炉水“变黑”原因分析及处理方法 被引量:1

Investigation and treatment of the‘black blower water' observed during pipe-blowing period of ultra-supercritical unit
下载PDF
导出
摘要 某电厂在吹管期间出现炉水"变黑"现象,为此对炉水进行了定性和定量分析。通过色谱分析法对炉水进行分析,发现炉水"变黑"的主要原因是铁氧化物含量过高。最后,提出了适当的处理方法,使得后续的吹管中未再出现炉水"变黑"现象。 During the pipe - blowing period of ultra water turned to black was observed. To deal with supercritical unit in the power plant,the boiler the problem, quantitative analysis was adopt- ed. Results of chromatographic analysis suggested the main cause of such phenomenon should be the excessively high level of iron oxide within the water, based on this consideration, a proper treatment method was purposed and problem was solved successfully
出处 《清洗世界》 CAS 2016年第3期42-45,共4页 Cleaning World
关键词 超超 临界机组 吹管 色谱分析 技术措施 ultra supercriticalunit pipe - cleaning chromatography technical installations