摘要
气-液旋流分离器内部流场复杂,结构尺寸等因素对其分离效率影响较大。针对排气管直径、插入深度、偏置角度、偏置距离以及增设底流口防返混锥5个结构因素进行正交试验设计,利用Fluent软件对16组有代表性的水平组合模型进行数值模拟,用极差法找出各因素优化水平组合以及各因素对分离效率和压降的主次影响顺序,最后通过综合平衡法找到最优组合,并分析了优选结构下液滴粒径和入口速度对分离效率的影响。
Gas-liquid cyclone separator has complex internal flow field,its separating performance is greatly affected by structural factors.In this paper,five structural factors were considered to carry out the orthogonal test design,including the exhaust pipe diameter,inserting depth,angle offset and offset distance and adding underflow anti back mixing cone.Through 16 groups of representative level combination model,numerical simulation was conducted using Fluent software.Moreover,the extremum difference analysis method was applied to find the factor combination mode and the influence sequence of each factor on separation efficiency and pressure drop.Finally,through the comprehensive balance method,the optimal factor combination mode was obtained and the effects of droplet size and inlet gas velocity on the separation efficiency were analyzed.
出处
《热力发电》
CAS
北大核心
2016年第3期41-47,53,共8页
Thermal Power Generation
关键词
气-液旋流分离器
分离效率
压降
正交试验
排气管
结构优化
gas-liquid cyclone separator
separation efficiency
pressure drop
orthogonal test
exhaust pipe
structure optimization