期刊文献+

一例典型的220kV架空线路档中跳接方式分析 被引量:1

Analysis on One Typical Span Jumper Connection Mode of 220kV Overhead Lines
下载PDF
导出
摘要 针对一例典型的220 kV架空线路档中跳接工程,为加快工程建设进度和节约成本,采用非耐张塔跳接方式。对这种跳接方式进行力学、电气和防雷计算,结果表明:跳接导线不会损坏原运行线路的导线和杆塔,连接金具可满足线路输送电流的要求,跳接线路处于避雷保护范围。指出施工中采用铝绞线、放松导线张力等措施可有效保护原导线,采用2根避雷线联合避雷方式可提高防雷效果。线路运行1个月后进行温度监测,结果显示线路处于正常运行状态。 In allusion to one typical span jumper connection of 220 kV overhead lines,tension tower jumper connection is used for quickening engineering construction progress and saving cost.Calculation on mechanics,electrical engineering and lightning protection is conducted for this kind of jumper connection mode,and results indicate that the jumper connection conductor would not damage conductors and towers of original running lines,connection of amour clamps may satisfy requirement for current transmission of lines and the jumper connection line lies in the range of lightning protection.It is pointed out that measures such as using all aluminium conductor(AAC)or releasing conductor tension may effectively protect original conductors,and it is able to improve lightning protection effect by using two lightning conductors combining with lightning protection mode.Temperature monitoring is carried out after lines running one month and results show lines are innormal states.
作者 刘俊勇 徐迎
机构地区 广州电力设计院
出处 《广东电力》 2016年第3期105-108,共4页 Guangdong Electric Power
关键词 架空线路 跳接 转角塔 直线塔 铝绞线 overhead line jumper connection angle tower straight line tower all aluminium conductor(ACC)
  • 相关文献

参考文献5

  • 1邵天晓.架空送电线路的电线力学计算[M].2版.北京:中国电力出版社,2009:89-91.
  • 2GB50545-2010110kV-750kV架空输电线路设计规范[S].北京:中国计划出版社,2010.
  • 3DL/T5154-2012架空送电线路杆塔结构设计技术规定[S].北京:中国电力出版社,2012.
  • 4DL/T5222-2005,导体和电器选择设计技术规定[S].北京:中国电力出版社,2005.
  • 5GB/T50064--2014,交流电气装置的过电压保护和绝缘配合设计规范[S].北京:中国计划出版社,2014:16-22.

共引文献10

同被引文献5

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部