期刊文献+

PTA装置雷达液位计假液位故障分析与控制 被引量:3

Fault analysis and control of false level indication of radar level gauge for PTA plant
下载PDF
导出
摘要 介绍了雷达液位计的测量原理及特点,以及雷达液位计在精对二甲酸(PTA)装置对二甲苯(PX)储罐液位测量中的应用,分析了雷达液位计液位测量时产生假液位的原因,并提出了相应的改进措施。结果表明:PX储罐内蒸汽在竖直壁面上冷凝而形成17~26 mm的液滴,因液滴尺寸大于雷达液位计发射波波长(12 mm),雷达发射波遇到液滴时产生反射回波,导致假液位的产生;选择频率为6 GHz,波长为50 mm的低频雷达液位计,将雷达天线由喇叭形改为直杆式,同时将PX储罐内温度由16~40℃提高至30~42℃,可有效避免PX储罐竖直壁面液滴产生的反射回波,控制雷达液位计假液位的产生;改进后的雷达液位计假液位故障明显减少,由改进前3次/d减少到改进后的(1~2)次/a,为PTA装置安全稳定运行提供了保障。 The measuring principle and characteristics of radar level gauge were introduced,as was the application of radar level gauge in the liquid level indication of p-xylene( PX) tank of purified terephthalaic acid( PTA) plant. The reasons for the false level indication of radar level gauge were analyzed,and the corresponding solution measures were put forward. The results showed that the false level indication occurred when the vapor in PX tank condensed into liquid droplets of 17- 26 mm on the vertical wall and the reflection echo returned from the liquid droplets due to their size higher than the emission wave length( 12mm) of radar level gauge; the reflection echo and the false level indication could be efficiently avoided by choosing the low-frequency radar level gauge with the frequency of 6 GHz and wave length of 50 mm,transforming trumpet antenna into rod antenna,elevating PX tank temperature from 16- 40 ℃ to 30- 42 ℃; and the false level indication could be profoundly depressed from 3times a day to once or twice a year after the improvement,which guaranteed the safe steady operation of PTA plant.
出处 《合成纤维工业》 CAS 2016年第2期60-63,共4页 China Synthetic Fiber Industry
关键词 精对苯二甲酸 雷达液位计 假液位 故障分析 控制 purified terephthalic acid radar level gauge false level fault analysis control
  • 相关文献

参考文献4

二级参考文献35

  • 1贾文超,宋丹,林晓梅.基于整周期自适应采样液位雷达信号处理算法[J].中国仪器仪表,2004(7):37-39. 被引量:1
  • 2刘凤仪.雷达液/料位实时测控装置[M].CN,2529216Y.2003.1.1.
  • 3G.S.Woods,D.L.Maskell,M.V.Mahoney.A high-accuracy microwave ranging system for industrial applications[J].IEEE Trans.Instrumentation and Measurement,1993,42(4):812-816.
  • 4Jing Yongqi,He Guoyu,Xu Yongbin.A FTDC technique to improve the range resolution of short range FMCW radar[C].2002 3rd international conference on microwave and millimeter wave technology proceedings.2002.480-483.
  • 5Zong Chengge,Yuan Yeshu,Zang Xinchao.A method for target estimation of level radar[C].CIE International Conference.1996.270-273.
  • 6Ren Kaichun,Zhang Xuanqi,Tu Yaqing.A method of estimating frequency of a frequency-modulation continuous-wave(FM-CW) radar level gauge under low signal-noise-ratio background[C].Proceedings of the 5th world congress on intelligent control and automation.2004.3765-3767.
  • 7D.L.Maskell,G.S.Woods,J-M Murray.A microprocessor controlled microwave ranging system for high accuracy industrial applications[C].Instrumentation and Measurement Technology Conference,1994,10th Anniversary Advanced Technologies in I & M.1994.1269-1272.
  • 8Qi Guoqing,Jia Xinle.Improvement of measurement accuracy of FMCW level radar[C].2001 CIE International Conference.2001.567-570.
  • 9Jorn Fuchs,Keith D.Ward,Marshall P.Tulin. Simple techniques to correct for VCO nonlinearities in short range FMCW radars[J].IEEE MTT-S Digest,1996,1175-1178.
  • 10J.C.Chun,T.S.Kim,Z.S.Lim.Spectrum correlation of beat signals in the FMCW radar level meter and application for precise distance measurement[J].IEEE MTT-S Digest,2001,2251-2254.

共引文献57

同被引文献18

引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部