期刊文献+

污水源热泵机组启动方式探讨 被引量:1

Discussion on Starting Mode of Sewage Source Heat Pump Unit
下载PDF
导出
摘要 通过对某一污水源热泵启动过程中断路器跳闸情况的研究,分析跳闸原因,发现开式星-三角降压启动方式在星形转三角形时二次冲击电流过大,提出采用闭式星-三角降压启动方式,减少在星形转三角形时的二次冲击电流,起到改善电网及减少设备危害的作用。 On the basis of research on breaker tripping during starting of one sewage source heat pump,tripping causes are analyzed,and then it is found that secondary impulse current is too high for open star-delta reduced voltage starting when the star starting is switched to the delta starting. This paper suggests the closed star-delta reduced voltage starting to reduce the secondary impulse current at switching,improve electric grid and relieve damages to equipment.
出处 《建筑电气》 2016年第4期51-56,共6页 Building Electricity
关键词 热泵机组 断路器跳闸 启动方式 降压启动 开式星-三角启动 闭式星-三角启动 过渡电阻 浪涌电流 heat pump unit breaker tripping starting mode reduced voltage starting open star-delta starting closed star-delta starting transition resistance surge current
  • 相关文献

参考文献7

  • 1中国航空工业规划设计研究院.工业与民用配电设计手册[M].第3版.北京:中国电力出版社,2005:17-18.
  • 2中国新时代国际工程公司.GB50055-201l通用用电设备配电设计规范[S].北京:中国计划出版社,2012.
  • 3舒向宇,陈洪亮.闭式星三角启动控制和转换电阻的计算[J].仪表技术,2008(3):27-29. 被引量:4
  • 4中机中电设计研究院有限公司.GB50054-2011低压配电设计规范[S].北京:中国计划出版社,2012.
  • 5中机中电设计研究院有限公司.GB50053-201320kV及以下变电所设计规范[S].北京:中国计划出版社.2014.
  • 6中国建筑东北设计研究院.JGJ16 - 2008民用建筑电气设计规范[J].北京:中国建筑工业出版社,2008.
  • 7张军涛.三相异步电动机Y/△降压启动控制线路常见故障分析[J].实验科学与技术,2013,11(4):19-21. 被引量:1