通过对某一污水源热泵启动过程中断路器跳闸情况的研究,分析跳闸原因,发现开式星-三角降压启动方式在星形转三角形时二次冲击电流过大,提出采用闭式星-三角降压启动方式,减少在星形转三角形时的二次冲击电流,起到改善电网及减少设备危害的作用。
On the basis of research on breaker tripping during starting of one sewage source heat pump,tripping causes are analyzed,and then it is found that secondary impulse current is too high for open star-delta reduced voltage starting when the star starting is switched to the delta starting. This paper suggests the closed star-delta reduced voltage starting to reduce the secondary impulse current at switching,improve electric grid and relieve damages to equipment.
出处
《建筑电气》
2016年第4期51-56,共6页
Building Electricity
关键词
热泵机组
断路器跳闸
启动方式
降压启动
开式星-三角启动
闭式星-三角启动
过渡电阻
浪涌电流
heat pump unit
breaker tripping
starting mode
reduced voltage starting
open star-delta starting
closed star-delta starting
transition resistance
surge current