摘要 医院净化空调系统负荷计算与普通空调系统负荷计算相比,具有风量仅取决于洁净度等级、湿度优先控制的特点,尤其是二次回风系统。因此,不能使用现有的常规空调系统计算软件进行负荷计算。为提高设计者工作效率,并保证设计的准确性,论文针对医院净化空调系统负荷计算开发了专用的计算软件,可生成标准化计算表格,并对该软件的计算原理进行说明。 Compared with the common air conditioning system load calculation, hospital purifying air-conditioning system has its characteristics. Firstly air volume only depends on the level of cleanliness classification, secondly the humidity should be controlled priority. The load calculation cannot use the existing calculation software for conventional air conditioning system especially in the secondary air returning system. In order to improve the Designers work efficiency, and ensure the accuracy of the design,we develop a calculation software in view of hospital purification air-conditioning system load calculation, generate standardized calculation form and illustrate calculation principle of the software.
出处 《工程建设与设计》 2016年第5期89-92,共4页 Construction & Design for Engineering
关键词 医院净化空调系统 负荷计算 计算软件 hospital purifying air-conditioning system load calculation calculation software
  • 相关文献

参考文献3

  • 1胡吉士.手术室洁净空调系统热湿处理过程探讨[J].暖通空调,2001,31(5):73-75. 被引量:20
  • 2刘拴强,刘晓华,江亿.温湿度独立控制空调系统在医院建筑中的应用方式研究2009[C]//.中国(上海)医院建筑设计及装备国际研讨会暨展示会论文集,2009.
  • 3GB 50333—2013,医院洁净手术部建筑技术规范[S].