期刊文献+

贵阳市2014年冷却塔水军团菌污染状况调查 被引量:3

Survey On Contamination Of Legionella Bacteria in Water of Cooling Towers in Guiyang in 2014
原文传递
导出
摘要 目的:了解贵阳市不同类型公共场所冷却塔水军团菌污染状。方法:随机对贵阳市39家公共场所冷却塔水进行采样,按照《公共场所集中空调通风系统卫生规范》附录B空调系统军团菌的检验方法对水样进行检测。结果:79份冷却塔水军团菌检出率为35.44%(28/79),阳性率以酒店最高,为41.51%(22/53)。军团菌血清LP1型占89.66%(26/29)、LP2型占10.34%(3/29)。冷却水消毒与不消毒、有无藻类生长对军团菌检出差异有统计学意义。结论:贵阳市不同公共场所冷却塔水中存在军团菌的污染,军团菌污染可能与冷却塔水不消毒、有藻类生长有关,可以为控制冷却塔水军团菌污染提供依据。 Objectives:To explore the contamination status and serological typing in water of various cooling tower in Guiyang . Methods: Legionella was detected in cooling water from 39 public place in Guiyang. LegioneUa was tested according to "Central Air Conditioning Ventilation System Hygiene Norms of Public Health Appendix B". Results: The detection rate of legionella in water of cooling towers was 35.44 ( 28/79 ), the positive rate was the highest in cooling water of hotels, which was41.51% (22/53) , respectively, the LP1 and LP2 were the serotype, accounted for89.66 (26/29)and10.34 (3/29), respectively. There were statistically significant dfference in the positive rate of [egionella between disinfected and non- disinfected water of cooling towers and between water with or without colonized algae. Conclusions: The water of oooling towers in Guiyang was contaminated severely. The proliferation of legionella is presumed due to unsatisfactory disinfection and colonized algae. The results provide the evidence for control of legionella pollution in water of cooling tower.
出处 《微量元素与健康研究》 CAS 2016年第3期50-51,共2页 Studies of Trace Elements and Health
基金 贵阳市科技计划项目(2013103第15号)
关键词 冷却塔水 军团菌 污染状况 Legionella Contamination condition Water of cooling tower
  • 相关文献

参考文献5

二级参考文献30

共引文献19

同被引文献37

引证文献3

二级引证文献17

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部