期刊文献+

探索沿地网对角布线的接地电阻测量

The Exploration about the Ground Resistance Measurement along the Diagnoal Line of Grounding Grid
下载PDF
导出
摘要 按照相关规范,常规的接地电阻测量的布线是测量线垂直地网边中点,电流测量线长度常是地网对角长度的2-3倍,但在实际的工作中,常遇不达测量要求的环境。针对这一问题,探索测量线沿地网对角线布置的方法,选择二小测量电流的接地电阻测量仪,测量一小地网的接地电阻并统计分析。结果:沿地网对角线布置且电流测量线长度是地网对角长度的2(3-4)倍和常规测量且电流测量线长度是地网对角长度的2(2-3)倍"总体均值无显著差异"。测量线沿地网对角线布置的可替代测量线垂直地网边中点的接地电阻测量。 It is recommend that the middle side of the grounding grid is vertical with measure line, the length of current measure line is 2 - 3 times than the length of the diagonal line of grounding grid, but required environment is not satisfied in the actual work. In view of the problem, it is explored about the ground resistance measurement along the diagonal line of grounding grid, Measurements and statistical analyses of a small grounding grid's ground resistance were done by choosing two kinds of small earth resistance meter. Conclusion: between the length of current measure line is 2 (3 -4) times than the length of the diagonal line of grounding grid and the length of current measure line is 2 ( 2 - 3 ) times than the length of the diagonal line of grounding grid, there is no significant difference in overall Average. The two methods can replace each other.
出处 《贵州气象》 2016年第2期85-88,共4页 Journal of Guizhou Meteorology
基金 福建省气象局基层专项(2015J03)资助项目
关键词 接地电阻测量 沿地网对角布线 方差分析 ground resistance measurement grounding grid along the diagonal line variance analysis
  • 相关文献

参考文献6

  • 1国家机械工业局.GB/T 179491 -2000接地系统的土壤电阻率、接阻抗和地面电位测量导则第一部分:常规测量[S].北京:中国标准出版社,2000.
  • 2中国气象局.GB/T21431 -2008建筑物防雷检测技术规范[S].北京:中国标准出版社,2008 :10 -11.
  • 3茅圣仁,杨超,林永强,等.4105A的建筑物接地电阻测量方法研究二[C]//第31届中国气象学会年会.北京:中国气象学会’2014.
  • 4廖文春,陈加清,陈岩,等.测量U形建筑基础接地电阻的有限差分分析[C]//第28届中国气象学会年会.厦门:中国气象学会’2011.
  • 5茅圣仁,许慧钦,陈文理,等+4105A的建筑物接地电阻测量方法研究[C]//第30届中国气象学会年会.南京:中国气象学会’2013.
  • 6苏理云,陈彩霞,高红霞.SPSS19统计分析基础与案例应用教程[M].北京:北京希望电子出版社,2012.