期刊文献+

煤气压缩机冷凝水收集池加设漏气回收装置

Adding a Leaked Gas Recovery Device to the Condensate Collecting Tank of Gas Compressor
下载PDF
导出
摘要 煤气压缩机冷凝水收集池残余煤气泄漏严重,造成区域一氧化碳含量超标,极易发生煤气着火、爆炸、中毒事故。采取了增加水封高度、安装污水吸出管、制作废气收集箱、设置废气溶解度气管等措施,解决了安全隐患。 Residual gas leaked heavily from the condensate collecting tank of gas com-pressor at Benxi Steel leading to excessive CO content in the area, which could easily cause gas fire, explosion or poisoning accidents. Measures such as adding higher water sealing, in-stalling wastewater suction tube, fabricating waste gas collecting boxes and setting up waste gas solubility tubes were taken, which have solved the safety risk.
出处 《冶金动力》 2016年第5期15-16,共2页 Metallurgical Power
关键词 煤气压缩水 冷凝水 泄漏 回收装置 gas compressing water condensate leakage recovery device
  • 相关文献

参考文献1

  • 1郭仁生.机械设计基础[M].北京:清华大学出版社,2006:19-23.

共引文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部