结合相关试验数据,从备用照明配电线路的供电连续性、末端线路短路保护灵敏度校验、设备机房检修、供电可靠性等方面探讨消防设备机房内部备用照明供电方案的合理性,建议消防设备机房内备用照明从机房内已设置的ATSE双电源切换箱后取得电源。
This paper, on the basis of relevant test data, explores the rationality of power supply plan for standby lighting in fire fighting equipment room from the aspects of power supply continuity of standby lighting distribution line, short circuit protection sensitivity of end line, equipment room maintenance and power supply reliability, and suggests that standby lighting in equipment room is supplied with power from ATSE double power switch box in the room.
出处
《建筑电气》
2016年第5期33-36,共4页
Building Electricity
关键词
消防设备机房
备用照明
供电连续性
绝缘失效
短路保护灵敏度
供电可靠性
设备检修
ATSE切换箱
耐火电线
fire fighting equipment room
standby lighting
power supply continuity
insulation failure
short circuit protection sensitivity
power supply reliability
equipment maintenance
ATSE switch box
fire resistant wire