一种基于锁相角扰动的主动式反孤岛策略

An active anti-island strategy based on phase-locked angle perturbation
下载PDF
导出
摘要 为减小并网电流畸变率,提高孤岛检测的响应速度,以满足不同类型负载的要求,提出一种基于锁相角扰动的主动式反孤岛策略。通过对参考电流锁相角引入一个微小的随正弦规律变化的扰动,使得参考电流到达峰值的时间向左或向右偏移,同时其频率又不受影响,由于逆变器输出电流是跟随参考电流的变化而变化,因而在主电网断电时,公共点电压过峰值的时间会有一个小角度的偏移,当偏移程度超过设定阈值范围,逆变器断开,停止向主电网供电。在PSCAD中搭建了单相光伏逆变器孤岛检测仿真模型,对多种类型的负载进行了仿真,结果表明,该方法具有对电网产生的谐波小、无检测盲区、算法简单易实现等优点。 To reduce the grid current distortion, improve the response speed of islanding detection and be able to fit different types of loads, an active anti-islanding strategy based on phase-locked angle disturbance is proposed. By introducing a slight sinusoidal variation disturbance into phase-locked angle, so that the reference current peak time will shift to the left or right, while frequency is not affected. Since the inverter output current will follow the change of the reference current, so when the grid is powered off, the common point overvoltage peak times will have a small angle shift. If the shift exceeds a set threshold range, inverter becomes disconnected and stops supplying power to the main power grid. A single-phase photovoltaic inverter islanding detection simulation model is built in the simulation platform of and simulations of different types of loads are conducted. The results show that this method has many advantages, such as small harmonics on the grid, no blind spot detection,algorithm is simple and easy to achieve, etc.
出处 《可再生能源》 CAS 北大核心 2016年第5期650-655,共6页 Renewable Energy Resources
基金 国际科技合作专项(2014DFG72240) 江西省自然科学基金(20151BAB206051)
关键词 单相光伏逆变器 反孤岛 锁相角扰动 电压过峰值时间 single-phase PV inverter anti-islanding phase-locked angle perturbation voltage peak time
  • 相关文献

参考文献6

二级参考文献55

  • 1郭小强,赵清林,邬伟扬.光伏并网发电系统孤岛检测技术[J].电工技术学报,2007,22(4):157-162. 被引量:111
  • 2IEEE Std 929-2000,IEEE recommended practice for utility interface of photovoltaic systems[S].
  • 3JERAPUTRA C,ENJETI P.Development of a robust anti-islanding algorithm for utility interconnection of distributed fuel cell powered generation[J].IEEE Transactions on Power Electronics,2004,19 (5):1163-1170.
  • 4OOI B T,SALMON J C,DIXON J W,et al.A three phase controlled current PWM converter with leading power factor[J].IEEE Trans Ind Appl,1987,IA223:78-84.
  • 5LULS L,SUN H.Pefformance assessment of active frequency drifting islanding detection methods[J].IEEE Trails on Energy Conversion,2006,21 (1):171-180.
  • 6EDUARDO ROMAN.Intelligent PV module for gridconnected PV systems[J].IEEE Transactions on industrial electronics,2006,53 (4):1066-1073.
  • 7陈卫民,陈国呈,吴春华,崔开涌,张翼,肖鹏.基于分布式并网发电的新型孤岛检测研究[J].电工技术学报,2007,22(8):114-118. 被引量:29
  • 8ROPP M E, BEGOVIC M, ROHATGI A. Determining the relative effectiveness of anti-islanding techniques using phase criteria and non-detection zones[J]. IEEE Transactions on Energy Conversion, 2000, 15(3): 290-296.
  • 9John Stevens, Russell Bonn, Jeny Ginn, et al. Development and testing of an approach to anti-islanding in utility-interconnected photovoltaic systems[M]. SAND 2000-1939, Photovoltaic System Application Department, Sandia National Laboratories, 2000.
  • 10Ropp M E. Design issues for grid-connected photovoltaic systems[D]. Atlanta: Georgia lnst Technol, 1998.

共引文献62

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部