摘要 交直流混联微电网是分布式发电(distributed generation,DG)装置并网的良好解决方式,因此,含DG的交直流混联微电网状态估计研究具有现实意义。针对换流器控制特性多样化及直流网络接入,该文提出适用于多种运行模式的交直流混联微电网状态估计模型。首先,针对微电网的孤岛运行特性,建立DG的Droop型节点模型。接着,根据交直流混联微电网状态估计的特点,配置相应的伪量测,以提高系统可观测性;同时采用了支路电流幅值量测转换法,以减少雅可比矩阵的求解难度。最后,采用最小二乘估计求解所提出的交直流混联微电网状态估计模型。通过IEEE13节点算例进行验证,结果表明,所提模型能够适用于并网和孤岛两种运行方式,具有良好的工程实用价值。 The AC-DC hybrid microgrid is the good solution for distributed generation( DG) paralleling in grid.Therefore,it is of great value to study the state estimation of AC-DC hybrid microgrid with DG. According to the control characteristic diversification of inverter and the integration of DC grid,this paper proposes a novel state estimation algorithm for the AC-DC hybrid microgrid considering operating status. Firstly,we establish the Droop-type node model of DG based on the islanded operating characteristics of microgrid. Furthermore,we formulate the appropriate pseudo-measurements to improve the system observability,according to the state estimation features of the AC-DC hybrid microgrid. M eanwhile,we use the branch current amplitude measurement conversion to reduce the difficulty of solving Jacobian matrix. Finally,we adopt the least square estimation to solve the proposed state estimation model of the AC-DC hybrid microgrid. The proposed models on grid-connected and islanded operation modes are tested on the modified IEEE-13 bus distribution system,whose results demonstrate the effectiveness of the proposed model in engineering applications.
出处 《电力建设》 北大核心 2016年第5期91-99,共9页 Electric Power Construction
基金 国家自然科学基金项目(51107032 61104045 51277052)~~
关键词 微电网 换流器 伪量测 分布式电源(DG) 状态估计 microgrid inverter pseudo-measurements distributed generation(DG) state estimation
  • 相关文献

参考文献22

  • 1王成山,王丹,周越.智能配电系统架构分析及技术挑战[J].电力系统自动化,2015,39(9):2-9. 被引量:97
  • 2刘杨华,吴政球,涂有庆,黄庆云,罗华伟.分布式发电及其并网技术综述[J].电网技术,2008,32(15):71-76. 被引量:207
  • 3郑漳华,艾芊.微电网的研究现状及在我国的应用前景[J].电网技术,2008,32(16):27-31. 被引量:265
  • 4KWASINSKI A. Quantitative evaluation of DC microgrids availability: Effects of system architecture and converter topology design choices[J]. IEEE Transactions on Power Electronics,2011, 26(3) :835-851.
  • 5刘家赢,韩肖清,王磊,张鹏,王靖.直流微电网运行控制策略[J].电网技术,2014,38(9):2356-2362. 被引量:141
  • 6ELSAYED A T, MOHAMED A A, MOHAMMED O A. DCmicrogrids and distribution systems:An overview[J]. Electric Power Systems Research ,2015 ( 119 ) :407 417.
  • 7GUERRERO J M, LOH P C, LEE T L, el al. Advanced control architectures for intelligent microgrids-part I1: power quality, energy storage, and AC/DC microgrids[J]. IEEE Transactions on Industrial Electronics, 2013,60 ( 4 ) : 1263 -1270.
  • 8LOH P C, LI D,CHAI Y K,et al. Aulononlous operation of ac dc microgrids with minimised interlinking energy flow [J].IET Power Electronics,2013,6( 8 ) : 1650-1657.
  • 9HUANG Y F, WERNER S, HUANG J, et al. State estimation in electric power grids., meeting new challenges presented by the requirements of the future grid [J]. Signal Processing Magazine, IEEE,2012,29(5) :33-43.
  • 10LU J,ZHU G, MIAO Y. State estimation of the micro-grid [ M ]. New York : Springer Verlag New York Inc,2014 : 517-527.

二级参考文献205

共引文献810

同被引文献27

引证文献3

二级引证文献14

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部