根据某水电站2台500 k V油浸式电力变压器及1台220 k V油浸式电力变压器本体介质损耗因数tanδ的测试数据,结合电介质介损的温度特性理论,综合分析变压器本体介损的温度特性与规程不符的可能原因。
Field tests are carried out to obtain the dielectric loss factor tanδ in the main bodies of two 500 kV and a 220 kV oil immersed power transformers in a hydropower station. According to the temperature characteristics theory of die- lectric loss, possible reasons of the difference between the actual temperature characteristics and the regulation are ana- lyzed.
出处
《水电与新能源》
2016年第5期61-63,66,共4页
Hydropower and New Energy
关键词
变压器
介质损耗
TANΔ
温度特性
原因分析
transformer
dielectric loss
tanδ
temperature characteristics