一起典型的GIS刀闸机构分闸位固死的故障处理及二次原理解析 被引量:3

Breaker Typical GIS with the Agency Break-brake Principle of Fault Handling and Secondary of the Fixed Die Parsing
下载PDF
导出
摘要 刀闸机构是GIS操作的重要部件,不能电动分合的故障时有发生,而产生故障的原因也有很多方面,此次缺陷原因非机械故障、非电机控制回路和电机转动回路的故障,是由电制动回路故障引起。下文将结合我局某变电站一起GIS刀闸机构分闸位固死故障为例,从多个角度寻找原因,最后再采取有效措施从根本上解决了问题,并提出了相关经验总结。 Isolating switch is an important part of a GIS operations,and cannot be electric points of failure occurs frequently,and the causes of failure also have a lot of ways,the defect reason not mechanical failure,motor control circuit and turn the circuit fault,is caused by electric braking circuit fault. Below will inform a substation combine with GIS isolating switch break-brake solid die failure as an example,from various angles to find the reason,and then take effective measures to fundamentally solve the problem,and puts forward the relevant experience.
作者 徐文
出处 《电气开关》 2016年第3期93-96,共4页 Electric Switchgear
关键词 GIS 刀闸机构 电制动 GIS disconnecting switch the electric brake