期刊文献+

变压器有载分接开关烧损事故分析 被引量:3

Analysis on On-load Decomposition Switch Burn-out Fault of Transformer
下载PDF
导出
摘要 针对一起220 k V变压器投运过程中有载分接开关烧损事故进行了分析,经现场检查与返厂解体,确认事故原因为变压器油含有杂质导致放电击穿,避免了事故的进一步发展,为今后220 k V变压器安全运行和技术监督积累了经验。 A 220 k V transformer' s on- load decomposition switch burn- out accident is analyzed,through on- site inspection and returned disintegration,the cause of the accident is identified as transformer internal discharge and breakdown caused by impurities in oil,the accident further development is avoided. The experience for the safe operation and technical supervision of the 220 k V transformer is accumulated.
出处 《东北电力技术》 2016年第4期33-34,52,共3页 Northeast Electric Power Technology
关键词 变压器 有载分解开关 杂质 Transformer On-load decomposition switch Impurities
  • 相关文献

参考文献5

二级参考文献31

  • 1周志强,韩洪刚,王海宽,程显福.一起电力变压器雷电过电压事故分析[J].变压器,2004,41(11):37-39. 被引量:9
  • 2陈化钢.电气设备预防性试验方法[M].水利电力出版社,1999.
  • 3电力设备预防性试验规程(DL/T596--1996)[s].中国电力出版社,1996.
  • 4A.c.富兰克林.D.P.富兰克林.变压器全书(中译本)[M].机械工业出版社,1990.
  • 5严璋.电气绝缘在线检测技术[M].中国电力出版社,1998.
  • 6ASTM D1275-2006,Standard Test Method for Corrosive Sulfur in Electrical Insulating Oils[S].
  • 7LIPSHTEIN R S,SHAKHNOVISH M I. Transformer oil [M]. The Second Edition. Jerusalem:Israel Program for Scientific Translation, 1970.
  • 8ROCHA A H. Faults in 500 kV shunt reactors caused by corrosive sulfur in the insulation oil[C]//Proceedings of the Sixty-eight Annual International Conference of Double Clients. Boston:[s.n.],2001: 4-5.
  • 9HAJEK J, BENNSTAM G, DAHLUND M, et al. Quality of oil makes the difference, ABB discovers the solution to transformer breakdowns[J]. ABB Review, 2004(4): 61-63.
  • 10PREVOST T A. Review of test method to detect corrosive sulfur in insulation oil[C]//Weidmann-ACTI Inc. Sixth An- num Technical Conference.Petersburg: [s.n.],2007:12-14.