期刊文献+

浅谈北海电厂300MW机组电除尘器的技术改造 被引量:1

Brief Discussion on Technical Modification of Electrostatic Precipitator of 300 MW Unit in Beihai Power Plant
下载PDF
导出
摘要 国投北部湾发电有限公司300 MW机组电除尘器实际出口烟尘排放浓度最高达120 mg/m3,已不能满足标准要求。对此,该电厂对电除尘器进行改造,将电除尘器的单相电源供电方式改造为三相电源供电方式,并对电除尘器一电场阴极系统进行分区改造。改造完成后,满负荷运行工况下电除尘器性能试验结果表明,电除尘器各个室进出口烟尘浓度、除尘效率均满足排放标准要求。 The highest value of actual outlet dust emission concentration of electrostatic precipitator of 300 MW unit in SDIC Beibuwan Power Generation Co., Ltd. has up to 120 mg/m3 which cannot meet requirements of standard. The modification of electrostatic precipitator in the power plant has been implemented, which changed the power supply mode from single- phase to threephase and modified the zone of electrostatic precipitator- electric field cathode system. After the modification, performance test results of electrostatic precipitator under full load operation condition show that dust emission concentrations at each inlet and outlet of electrostatic precipitator and dust precipitation rate all met requirements of emission standard.
出处 《广西电力》 2016年第3期54-56,65,共4页 Guangxi Electric Power
关键词 电除尘器 供电方式 电场分区 electrostatic precipitator power supply mode electric field zone
  • 相关文献

参考文献5

  • 1王荣华,闫克平.利用三相电源改造电除尘器实现节能和减排[c].中国环境科学学会学术年会优秀论文集,2008:208-210.
  • 2王成福,施晓东,祝建军.电除尘三相高压电源节能与提效研究[J].金华职业技术学院学报,2009,9(3):23-28. 被引量:1
  • 3马川,陶学恒,李晓峰,李宝营.静电除尘器用三相高压整流设备应用分析[J].机电产品开发与创新,2010,23(1):50-51. 被引量:2
  • 4张小娟,高继贤,阎冬.一种湿式电除尘器分区供电系统及分区供电方法[P].中国,cNl04525376A,2015-04-22.
  • 5李宝才,李洋,李健.一种分区供电静电除尘器[P].中国,CN202070401U.2011-12-14.

二级参考文献3

  • 1王成福.电除尘器高压供电优化控制仿真研究[J].计算机仿真,2007,24(4):240-242. 被引量:5
  • 2高香林,胡志光.电除尘器供电控制技术[J].华北电力学院,1991,6.
  • 3张谷勋,蒋云峰,董逢武.高压静电除尘设备电源的新模式中国当代思想宝库[M].中国文联出版社,2006.

共引文献1