期刊文献+

逆流降膜热质交换的数值模拟和实验研究 被引量:1

Numerical Simulation and Experimental Study of Heat and Mass Transfer in Counterflow Falling Film
下载PDF
导出
摘要 针对对流传热边界条件,本文建立了一种平板逆流交换器的数值模型,分析了溶液温度场、浓度场和空气温度场的分布规律。采用氯化锂溶液作为除湿剂,通过实验方法进行验证,结果表明:97%的除湿和再生效率实验结果和计算结果偏差在20%以内,平均偏差约为7.8%,计算结果和实验结果吻合较好,数学模型基本反应了热质交换过程的变化规律。 For convective heat transfer boundary conditions,a numerical model of a plate counterflow exchanger is established in this paper. Distribution law of Solution temperature and concentration field and air temperature field is analyzed. Then using lithium chloride solution as desiccant,the model is validated by experimental method. The re-sults shows that the deviation of 97%experiment values and calculated values of the dehumidification and regenera-tion efficiency is within 20%,and the average deviation is about 7.8%. The calculation results and experimental results are in good agreement,which means the change rule of heat and mass transfer process is basically reflected by this model.
出处 《制冷》 2016年第2期6-11,共6页 Refrigeration
关键词 逆流 传热传质 数值模拟 除湿 Counterflow Heat and mass transfer Numerical simulation Dehumidification
  • 相关文献

参考文献7

  • 1R. E. Treybal. Adiabatic gas absorption and stripping in packed towers. Industrial and Engineering Chemistry. 1969:61-68.
  • 2H. M. Factor and Gershon Grossman. A packed bed de- humidifier/regenerator for solar air conditioning with liquid desiccants. Solar Energy, 1980 : 541 - 550.
  • 3P. Oandhidasan, C. F. Kettleborough and M. Rifat U1- lah. Calculation of heat and mass transfer coefficients in a packed tower operating with a desiccant - air contact sys- tem. Solar Energy Engineering, ASME, 1986: 123- 127.
  • 4Oberg, V. , Goswami, D. Y. , 1998b. Experimental study of heat and mass transfer in a packed bed liquid desiccant air dehumidifier. Transactions of the ASME Journal of So- lar Energy Engineering. 1998b, 289 -297.
  • 5Sadasivam, M., Balakrishnan, A. R. Effectiveness- NTU method for design of a packed bed liquid desiccant de- humidifiers. Transactions of the Institution of Chemical Engineers. 1992 : 572 - 577.
  • 6Khan, A. -., Ball, H. D., Development of a general- ized model lbr performance evaluation of packed - type liq- uid sorbent dehumidifiers and regenerators. ASHRAE Transactions. 1998:525 -533.
  • 7Patankar, S: V. , Numerical heat transfer and fluid flow. Hemisphere, Washingtong, D. C., 1980.