期刊文献+

电网谐波对级联STATCOM运行影响分析及抑制 被引量:2

Effect of System Voltage Harmonics on Cascaded STATCOM DC Voltages Balancing and Its Suppression Strategy
下载PDF
导出
摘要 采用移相载波调制算法的链式静止同步补偿器(STATCOM)每相各链节之间交流输出电压中同频次谐波分量存在相位差,当电网中存在相应频次的电压谐波并使得STATCOM产生谐波电流时,会造成各链节与系统之间交换幅值不同的谐波有功。当STATCOM在低载输出工况时,由于链节直流电压均衡控制策略效果的弱化,使得谐波有功对链节直流电压的影响增大,这时差异化的谐波有功会使得链节间直流电压逐渐发散,并使得设备失稳。这里分析了采用移相载波调制算法的链式STATCOM在系统电压存在谐波情况下各链节谐波有功的差异,指出了链节直流电压均衡策略对此问题的缺陷,提出对应的解决策略,在PSCAD/EMTDC环境中进行了仿真验证,并在实际工程应用中有效解决了相关问题。 Output harmonic voltage between links of cascaded static synchronous compensator(STATCOM) by using muhi- carrier horizontal phase-shifting modulation exist phase difference.When power system has harmonic voltage,STATCOM will output corresponding frequency harmonic current, it will cause different active power exchange between links and system.Then the voltages of links will gradually diverge, when STATCOM under low load output condition, due to the direct current link voltage balance control strategy's weakness.The effect of system voltage harmonics to STATCOM links' direct current voltages balancing is analyzed, a corresponding solution strategy is given, and the simulation confir- mation in PSCAD/EMTDC is carried out.In practical engineering application, the related problems are solved effectively.
出处 《电力电子技术》 CSCD 北大核心 2016年第8期31-34,共4页 Power Electronics
关键词 静止同步补偿器 均压 谐波 载波移相 static synchronous compensator voltages balancing harmonics carrier horizontal phase-shifting
  • 相关文献

参考文献3

二级参考文献9

  • 1Zhang H, Jouanne A, Dai S, et al. Multilevel inverter modulation schemes to elimination common-mode voltages[J]. IEEE Trans on Ind Appl. 2000, 36 (6): 1645 - 1653
  • 2Holtz W., Lotzkat, K. H. Werner. A high-power multi transistor-inverter uninterruptible power supply system[C]. Proceeding of IEEE PESC. 1986: 311 -320
  • 3J. S. Lai, F. Z. Peng. Multilevel converters-a new breed of power converters[J]. IEEE Trans Ind Applicat. 1996, 32(2): 509 - 517
  • 4Jose Rodriguez, Jih-Sheng Lai, Fang Zheng Peng. Multilevel inverter: a survey of topologies, controls, and Applications[J]. IEEE Trans on Industrial Electronics. 2002, 49 (4) : 724 - 738
  • 5Liang Yiqiao, Nwankpa CO. A new type of STATCOM based on cascading voltage-source inverters with phase-shifted unipolar SPWM[J]. IEEE Trans on Ind Applicat. 1999,35(5): 1118-1123
  • 6Meynard T A, Fadel M, Aouda N. Modeling of Multilevel Converters. IEEE Trans on Industrial Electronics, 1997, 44(3).
  • 7Peng F Z, Lai J S. Dynamic Performance and Control of a Static Var Generator Using Cascade Multilevel Inverters. IEEE Trans on Industry Applications. 1997, 33(3) : 748-755.
  • 8Woodhouse M L, Donoghue M W, Osborne M M. Type Testing of the GTO Valves for a Novel STATCOM Convertor. AC-DC Power Transmission. In: Seventh International Conference on AC-DC Power Transmission (IEE Conference Publication No485). London (UK): IEE, 2001. 84-90.
  • 9耿俊成,刘文华,袁志昌.链式STATCOM电容电压不平衡现象研究(一)仿真和试验[J].电力系统自动化,2003,27(16):53-57. 被引量:91

共引文献72

同被引文献16

引证文献2

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部