期刊文献+

通风系数对钢构件的耐火性能影响研究

On the Effect of Ventilation Coefficient to the Fire Resistance of a Steel Component
下载PDF
导出
摘要 为准确评估钢构件在室内火灾时的耐火性能,以室内火灾轰燃后的房间热平衡和热传导理论为基础,计算了火灾荷载为800 MJ·m^(-2),通风系数分别为0.03、0.05、0.08和0.1 m^(1/2)时的室内平均温度,以此为火作用,基于传热学基本理论,分别编程计算了方矩钢管柱在防火保护情况下的平均温度-时间曲线,对比分析了通风系数对钢构件温度的影响。结果表明:虽然通风系数较大时火灾温度较高,但由于火灾持续时间较短,钢构件最高温度较低,较通风系数较小时更偏于安全。 To accurately evaluate the fire resistance of a steel component in compartment fire, the average tempera-ture of the compartment was calculated, based on the theories of heat balance of compartment post - flashover and heat conduction, in which the fire load density was 800 MJ·m^-2 and the ventilation coefficient were 0. 03 , 0. 05, 0. 08 and 0. 1 m^1/2. Based on the theories of heat transfer, the average temperature - time curves of the quadrate steel column were calculated by program in the fire load of these temperatures of the compartment. And the effect of ventilation coefficient to the temperature of the column was analyzed. The results show that when the ventilation coef-ficient is big, the temperature of the compartment fire will be high, but, the time of the fire persisted will be short, and the highest temperature of the steel column will be low. So the steel structure will be safer in the situation.
作者 朱婉婉
出处 《武警学院学报》 2016年第8期9-12,共4页 Journal of the Armed Police Academy
关键词 钢构件 火灾荷载 通风系数 传热学 耐火性能 steel component fire load ventilation coefficient heat transfer fire resistance
  • 相关文献

二级参考文献3

  • 1俞昌铭.热传导及其数值分析[M].北京:清华大学出版社,1988..
  • 2Magnusson, S. E. and Thelandersson, S. Temperature - Time Curves for Complete Process of Fire Development. A theoretical study of Wood Fuel Fires in Enclosed Spaces. Acta Polytechnicia Scandinavica,Ci 65,Stockholm 1970
  • 3公安部天津消防科研所.钢筋混凝土构件耐火性能试验研究(内部报告),1992-1993

共引文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部