期刊文献+

一组SF_6气体湿度测试异常数据的分析 被引量:1

Analysis on a Group of Abnormal Data of Humidity Measurement of SF_6 Gas
下载PDF
导出
摘要 在用冷凝式露点仪对某500 k V变电站组合电器进行湿度测试时,发现部分气室湿度超标,用阻容湿度仪测试的数据却在合格范围内。通过3台仪器现场对比测试及分析,确定数据差异是因所用仪器原理不同和露点仪使用不规范造成的。总结现场测试SF6气体湿度注意事项,为技术人员提供参考。 A part of GIS chamber humidity of one 500 k V substation exceeded the standard when it was tested by a condensation dew point instrument,however,when tested by using resistance capacity humidity instrument,the data were in the qualified range.Through contrast between three humidity instruments,it is concluded that the data difference was caused by different principle of humidity instrument and non-standardized operation.Points for attention are summarized for humidity measurement of SF6 gas in substation,which could provide references for the tester.
出处 《山西电力》 2016年第4期28-30,共3页 Shanxi Electric Power
关键词 SF6气体湿度测试 露点法 阻容法 humidity measurement of SF6 gas dew point method resistance capacity method
  • 相关文献

参考文献4

二级参考文献9

  • 1DL/T596-1996.电力设备预防性试验规程[S].[S].,..
  • 2DP-19-SH-Ⅲ 露点仪使用说明书[Z].
  • 3GB 8905-1996,六氟化硫电气设备中气体管理和检测导则检测标准与周期[S].
  • 4DP99-Ⅲ型数字智能露点仪使用说明书[Z].
  • 5DL/T 956-1996.电力设备预防性试验规程[S].
  • 6钟志铿,姚唯建.对运行设备中SF6含水量指标与测试条件的一些看法[C]//电力部SF6气体监督检测技术研讨会论文集.西安:电力部热工研究院,1996:61-65.
  • 7GB/T 8905-1996.SF6电气设备中气体管理和检测导则[S].
  • 8任玉刚,沈荣顺,李新春,赵忠远.DP19-III型微水仪使用中存在的问题及对策[J].河北电力技术,2000,19(6):20-21. 被引量:2
  • 9陆明,柯建国,朱琴.DP19露点仪测试中的一个问题[J].电力安全技术,2002,4(4):34-34. 被引量:4