期刊文献+

空调器制冷量不确定度评定

Uncertainty Evaluation for Cooling Capacity of Air-conditioner
下载PDF
导出
摘要 空调器制冷量测试的结果受到很多因素的影响,其结果很大程度上影响整机的能效等级评定。首先介绍了最新版空气焓差法测量制冷量的数学模型;其次,对额定制冷量为2.7 k W的房间型空气调节器的制冷量测试结果进行了不确定度评定;最后,讨论了影响实验数据不确定度的主要因素。分析给出的测试数据得出如下结论:在空调器制冷量测试中,进出口湿球温度对制冷量测量影响最大,其次为A类不确定度,喷嘴前压差、大气压力及喷嘴直径,其余参数对制冷量的影响可以忽略。 The cooling capacity test result of air-conditioner is affected by many factors, and the result has great influence on the energy efficiency rating. Firstly, we introduce the mathematical model of latest air enthalpy difference method for measuring cooling capacity; secondly, the evaluation of uncertainty of the room air-conditioner whose cooling capacity is 2.7 kW was carried out; at last, the main factors that affect the uncertainty of the experimental data are summarized. Analysis of test data in this paper draws the following conclusions: in the testing process of air-conditioner cooling capacity, inlet and outlet wet bulb temperature has the greatest impact on cooling capacity, followed by type A uncertainty, the nozzle pressure difference, atmospheric pressure and nozzle diameter, and the remaining parameters influence on cooling capacity can be ignored
作者 邵伟恒 邵鄂
出处 《环境技术》 2016年第4期38-41,共4页 Environmental Technology
关键词 焓差法 空调器 制冷量 不确定度 enthalpy difference method air-conditioner cooling capacity uncertainty
  • 相关文献

参考文献6

二级参考文献8

  • 1樊高定,贾磊,钱雪峰,王溢芳,舒国安.空气焓值法测量空调制冷量的不确定度评定[J].流体机械,2007,35(6):62-65. 被引量:14
  • 2GB/T7725-2004《房间空气调节器》[S].北京:中国标准出版社,2004.
  • 3CNAS-GL02《能力验证结果的统计处理和能力评价指南》[S].北京:中国知识出版社,2006.
  • 4《测量不确定度评定与表示指南》[M].北京:中国计量出版社,2005.
  • 5JJF 1059-1999《国家质量技术监督局计量司组测量不确定度评定与表示》[M].北京:中国计量出版社,1999.
  • 6中国国家标准化管理委员会.GB/T 7725-2004 房间空气调节器[S],2004
  • 7JJF1059.1-2012,测量不确定度评定与表示[S].北京:国家质量监督检验检疫总局,2011.
  • 8李敏毅,刘定强,梁显有.空调器空气焓差法测量制冷(热)量方式及误差分析[J].实用测试技术,2002,28(3):24-26. 被引量:23

共引文献60

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部