变压器油纸绝缘热电联合老化特征量研究 被引量:6

Study on Thermo-electrical Aging Characteristics of Transformer Oil-paper Insulation
下载PDF
导出
摘要 为研究电力变压器油纸绝缘在热、电两种应力作用下的老化特性,搭建了油纸绝缘热电联合老化试验平台,设计了两组在130℃下进行的加速老化试验:一组是单因子热老化试验,另一组为热电联合老化试验。通过对两组老化样本的绝缘纸聚合度、击穿电压、油中微水含量等参数进行对比分析,结果表明,热电联合老化样本绝缘纸聚合度下降速度比热老化样本要快,且在老化初期绝缘纸击穿电压与绝缘纸聚合度呈一定线性关系,与油中水分含量则没有明显的直接联系。 In order to study on thermo-electrical aging of transformer oil-paper insulation, a test platform for thermo-electrical aging of oil-paper insulation is set up, and two groups of accelerated aging test are designed under 130℃. One is thermal aging test, the other is thermo-electrical aging test. By the comparison of two aging tests, the result shows that DP of paper under thermo-electrical stress decreases faster than that under single thermal stress. The breakdown voltage of paper has a linear relation with DP but no significant relationship with water content in oil at the beginning of the aging progress.
作者 张宇航 兰生
出处 《电气技术》 2016年第7期48-51,61,共5页 Electrical Engineering
基金 福建省自然科学基金(2015J01194)
关键词 电力变压器 油纸绝缘 热电联合老化 击穿电压 power transformer oil-paper insulation thermo-electrical aging breakdown voltage
  • 相关文献

参考文献9

二级参考文献48

共引文献157

同被引文献68

引证文献6

二级引证文献58