摘要
以实际生活污水处理为研究内容,考察了不同进水点对A-A^2/O系统生物脱氮除磷的效果,结果表明,进水流量分配对系统去除COD_(Cr)及NH_3-N影响不明显,对总氮和总磷去除则影响明显;缺氧区增加进水有利于为缺氧段的反硝化脱氮提供充足的碳源,进而提高反硝化速率和实现高效脱氮;分段进水有利于碳源的合理分配。
Using domestic sewage with low C/N as treatment objective,the performance of A-A^2/O process for denitrification and phosphorus removal was investigated. The results showed that the inflow distribution ratio value had less effect on removal of CODCrand NH3-N than TN and TP. Increase inflow distribution ratio in the anoxic tank is conducive to provide adequate carbon source for the denitrification anoxic,thereby increasing the rate of denitrification and efficient denitrification,indicating step feed conducive to the rational allocation of carbon source.
出处
《山西建筑》
2016年第26期136-137,共2页
Shanxi Architecture
基金
国家"水体污染控制与治理"科技重大专项(项目编号:2013ZX07314-001-003)
城区水污染过程控制与水环境综合改善技术集成与示范(项目编号:2012ZX07301-001)
关键词
A-A^2/O工艺
进水流量分配
脱氮除磷
A-A2/O process
inflow distribution ratio
nitrogen and phosphorus removal