期刊文献+

基于电网不平衡APF系统新型锁相环的研究 被引量:1

Research on a Novel Phase-locked Loop Based on Unbalanced Grid APF System
下载PDF
导出
摘要 此处提出了一种改进的三相低通陷波器(LPN)锁相环(PLL)方法,该方法基于Clarke交换和Park变换,通过LPN滤波器,从而消除电网不平衡电压中的零序和负序分量。详细分析了单相LPN-PLL方法在电网不平衡条件下无法准确得到基波正序电压相位的原因及单相LPN-PLL相位偏差对i_p-i_q谐波检测的影响。详细分析了所提三相LPN-PLL的原理及所选滤波器的截止频率对三相LPN-PLL性能的影响和三相LPN-PLL的动态性能。通过仿真和实验分别验证了所提出的三相LPN-PLL方法能较好地检测出基波正序相位。将其应用到有源电力滤波器(APF)系统中,通过采用i_p-i_q谐波检测方法,能达到较好的补偿效果。 An improved method for three-phase low pass noteh(LPN) phase-locked loop(PLL) is proposed.Based on Clarke and Park transformations, unbalanced grid voltage zero-sequence and negative sequence components can be el- iminated through LPN fiher.Firstly, under the unbalance condition,the reason that single-phase LPN-PLL can not ac- curately get the phase of fundamental positive sequence voltage and the influence of single-phase LPN-PLL phase difference to ip-iq harmonic detection are analyzed.The principle of the proposed three-phase LPN-PLL, the influence of cut-off frequency to three-phase LPN-PLL characteristic and the dynamic characteristic of three-phase LPN-PLL are analyzed.Simulation and experimental results show that the fundamental positive sequence phase can be accurately obtained by the improved three-phase LPN-PLL method.The method is used in active power fiher(APF) system,it can get better compensation effect through ip-iq harmonic detection method.
机构地区 中国矿业大学
出处 《电力电子技术》 CSCD 北大核心 2016年第9期35-38,47,共5页 Power Electronics
基金 国家自然科学基金(51407183)
关键词 锁相环 基波正序相位 有源电力滤波器 phase-locked loop fundamental positive sequence phase active power filter
  • 相关文献

参考文献7

  • 1Parag Kanjiya,Vinod Khadkikar,Hatem H Zeineldin.A Noniterative Optimized Algorithm for Shunt Active Pow- er Filter Under Distorted and Unbalanced Supply Volt- ages [J].IEEE Trans. on Industrial Electronics, 2013,60 (12) : 5376-5390.
  • 2Yuan Xiaoming, Merk W, Stemmler H, et al.Stationary Frame Generalized Integrators for Current Control of Ac- tive Power Filters With Zero Steady-state Error for Cur- rent Harmonies of Concern Under Unbalanced and Dist-orted Operating Conditions[J].IEEE Trans. on Industry Ap- plications, 2002,38 ( 2 ) : 523-532.
  • 3Sang-Joon Lee, Jun-Koo Kang, Seung-Ki Sul.A New Phase Detecting Method for Power Conversion Systems Consid- ering Distorted Conditions in Power System[A].Proc. In- dustry Applications Conf., 34th IAS Annual, Meeting[C]. 1999 : 2167-2172.
  • 4Rodriguez P,Teodorescu R, Candela, et al.New Positive- sequence Voltage Detector for Grid Synchronization of Power Converter Under Faulty Grid Condition[A].Power Electronics Specialists Conference[C].2006 : 1-7.
  • 5Karimi Ghartemani M,Iravani M R.A Nonlinear Adapti- ve Filter Foronline Signal Analysis in Power System: Applications[J].IEEE Trans. on Power Del., 2002, 17 (2) : 617-622.
  • 6Rodriguez P, Luna A, Ciobotaru M, et al.Advanced Grid Synchronization System for Power Converters Under Un- balancedand Distorted Operating Conditions[A].In Proc. 32nd IEEE Int. Conf. Ind. Electron,Control,Instrum.[C]. 2006 : 5173-5178.
  • 7Kyoung-Jun Lee, Jong-Pil Lee, Dongsul Shin, et al.A No- vel Grid Synchronization PLL Method Based on Adaptive Low-pass Notch Filter for Grid-Connected PCS[J].IEEE Trans. on Industrial Electronics, 2014,61 ( 1 ) : 292-300.