摘要 本文简要介绍了人防柴油电站的温湿度要求及散热量,以及消除余热量所需的计算通风量。为排除柴油发电机房内余热和有害气体,提供柴油机燃烧所需要的空气,应对柴油电站进行通风量计算。如果柴油机机头散热器热量直接由与之相连的风管排到室外,这时机房进风量分别按机头散热器排风量和排除机房内余热进风量考虑,取其中较大者。 In this paper, the requirement of temperature and humidity and the amount of heat dissipation of the air defense diesel power station are briefly introduced. In order to eliminate the waste heat and harmful gas in the diesel generator room, the air needed by the diesel engine combustion is provided to deal with the calculation of the ventilation rate of the diesel power station. If the heat of the diesel engine is directly connected with the air pipe, the air volume of the engine room is in accordance with the air volume of the head radiator and the waste heat of the waste heat in the engine room.
作者 宁涛 陈雯 NING Tao CHEN Wen(Construction Engineering Research Institute of the General Logistics Department,Xian 710032 Shaanxi Provincial Sports Training Center, Xian 710065)
出处 《移动电源与车辆》 2016年第2期50-52,共3页 Movable Power Station & Vehicle
关键词 人防工程 柴油电站 通风量 Civil air defense project diesel power station ventilation