期刊文献+

采用TEV传感器的开关柜局部放电检测技术研究与实现 被引量:18

Research and Implementation of Partial Discharge in HV Switchgear Using TEV Sensor
下载PDF
导出
摘要 分析了开关柜内发生局部放电时柜体表面产生暂态地电压原理及TEV传感器设计原理。依据设计原理研制了一种TEV传感器,运用TEV传感器对3种典型开关柜缺陷模型进行了试验研究。并对放大检波前后的TEV信号进行了分析。基于所设计的TEV传感器、放大检波电路以及超声波法研制了一套开关柜局部放电检测装置,并运用该装置对多个变电站进行了实测。结果表明:TEV原始信号幅值低于100mV,能量分布在3~200MHz之间;所设计的放大检波电路提高了原始TEV信号的信噪比,降低了采集难度,试验研究和现场测试验证了该套检测装置的有效性。 The mechanism of transient earth voltages(TEV)aroused by partial discharge in switchgears and the design mechanism of the TEV sensor are analyzed, the TEV sensor is designed according to its design mechanism and is used to record the TEV information corresponding to three typica PD models in HV switchgears. The origi- nal and after-amplifying-modulating TEV signal is analyzed. Detection system is developed combining with TEV sensor, amplifier demodulation and AE method. The system has been tested in several substations. The results show that, the amplitude of TEV original signal is lower than 100 mV, the energy distribution is lied in the frequency of 3 MHz to 200 MHz. The designed amplification demodulation circuit has improved the SNR and reduced the difficulty of collecting: Experimental research and field application verify the effectiveness of the system.
出处 《高压电器》 CAS CSCD 北大核心 2016年第10期19-26,共8页 High Voltage Apparatus
基金 国家高技术研究发展计划项目(863计划)(2012AA050802)~~
关键词 开关柜 局部放电 TEV传感器 缺陷模型 放大检波 HV switchgears partial discharge TEV sensor defects model amplifier demodulation
  • 相关文献

参考文献22

  • 1王飞鸣,林莘,谢寅志,徐建源,王娜.特高压半封闭气体绝缘组合电器的暂态电压仿真分析[J].高电压技术,2012,38(2):407-413. 被引量:13
  • 2程述一,律方成,谢庆,王子建,李燕青,杨海涛.基于暂态对地电压和超声阵列信号的变压器局放定位方法[J].电工技术学报,2012,27(4):255-262. 被引量:33
  • 3任明,彭华东,陈晓清,董明.采用暂态对地电压法综合检测开关柜局部放电[J].高电压技术,2010,36(10):2460-2466. 被引量:146
  • 4JAMES J, KULKARNI S V, PAREKH B R. Partial dis- charge in high voltage equipments-HV cable [C]//2009 IEEE 9th International Conference on the Properties and Applications of Dielectric Materials. Harbin : IEEE, 2009 : 445 -448.
  • 5ELEb-THERION P M. Partial discharge. XXI: Acoustic emission based PD source location in transformers[J]. IEEE Transactions on Electrical Insulation Magazine,1995,11 (6): 22-26.
  • 6. WITOS F, GACEK Z, MALITOWSKI G A, et al. Partial discharges investigation in the power transformer by means of joint electro-acoustic method assisted by chromatogra- phy method[J]. Przeglad ELektrotechniczny, 2010,86(11 B): 13-16.
  • 7曾雄杰,江健武,侯俊.TEV和UHF在10kV开关柜带电检测中的应用[J].高压电器,2012,48(1):41-47. 被引量:54
  • 8FASIL V K, KARMAKAR S. Modeling and simulation based study for on-line detection of partial discharge of solid dielectric[C]//2012 IEEE 10th International Confer- ence on the Properties and Applications of Dielectric Ma- terials. Bangalore, India: IEEE, 2012:1-5.
  • 9KURIMSKY J, KOLCUNOV I, CIMBALA R. Under- standing surface partial discharges in HV coils and the role of semi-conductive protection[J]. Electrical Engineer- ing, 2010, 92(7-8): 283-289.
  • 10AZEVEDO C H B,MARQUES A P,RIBEIRO C J. Methodology for the detection of partial discharges in pow- er transformers using the acoustic method [C]//EUROCON 2009.Russia: IEEE, 2009: 618-621.

二级参考文献169

共引文献374

同被引文献121

引证文献18

二级引证文献93

相关作者