摘要 为适应跨区特高压互联大电网的发展,深度理解特高压复奉、锦苏、宾金直流对华北-华中-西南链式交流同步电网的影响,从跨区多条直流连续多次、同时换相失败的机理入手,研究导致特高压复奉、锦苏、宾金直流连续多次、同时换相失败的华东电网故障,以及对华北-华中-西南链式交流同步电网产生的冲击,并找出了减小影响的有效措施:延长华东线路重合闸间隔时间、配置安控切机措施、及根据四川南部、重庆开机容量,合理规定华北-华中-西南链式交流同步电网跨区联络线的稳定限额。 To adapt the development of cross UHV interconnected power grid, and find out the impact of UHVDC Fufeng, Jinsu and Jinbin to North-Central-Southwest China AC synchronous grid, we researched the mechanism of repeatedly and simultaneous commutation failure in multiple HVDC power transmission system between two regional power grids, and failure of East China power grid dued to repeatedly, simultaneous commutation failure in UHVDC Fufeng, Jinsu and Jinbin between Sichuan power grid and East China power grid, and the impact of North-Central-Southwest China AC synchronous grid. Meanwhile, we took effective measures to reduce the impact, including prolonging the time interval between the time of the lock of the East China line, and configuring security control measures cutting machine. Moreover, according to southern Sichuan, Chongqing power capacity, we reasonably required the stability limit of cross-tie line of North-Central-Southwest China AC synchronous grid.
出处 《高电压技术》 EI CAS CSCD 北大核心 2016年第10期3315-3320,共6页 High Voltage Engineering
关键词 特高压直流 换相失败 多馈入 交直流电网 强直弱交 UHVDC commutation failure mutil-Infeed AC/DC power grid weak AC and strong DC grid
  • 相关文献

参考文献14

二级参考文献185

共引文献713

同被引文献200

引证文献11

二级引证文献146

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部