一种换流变压器零序过流保护改进方案 被引量:1

An Improved Scheme for Zero-sequence Over-current Protection of Converter Transformers
下载PDF
导出
摘要 针对某换流站换流变压器空充时零序过流保护误动这一事故,根据故障录波器波形证实了此次保护为正确动作。通过对比发现:国家电力调度继电保护处和南方电网电力调度继电保护处,在整定换流变零序过流保护时基于的整定原则不一致。经优化零序过流保护逻辑,将空充标志状态引入零序过流保护,使得保护装置能够在判别出换流变处于空充时自动投入零序过流保护的二次谐波闭锁功能,正常运行时退出保护的二次谐波闭锁功能。既能确保空充时零序过流保护不误动,又能保证正常情况下发生接地故障时零序过流保护的可靠性。最后通过将故障录波器波形进行故障回放验证了方案的正确性。 With respect to a maloperation of zero-sequence over-current protection of the converter transformer at a converter station during transformer charging, the waveform from the fault oscillograph verifies that it is a correct protection action. Through comparison, it is found that the power dispatch relay protection &.partment of the State Power Grid and that of the China Southern Power Grid apply different principles for setting zero-sequence ow'r-current protection for the converter transformer. Though optimization of the zero- sequence over-current protection logic1 zero-sequence over-current protection is applied to the charging mark state1 so that the protection device can automatically initiate second harmonic lock for zero-sequence over-current protection when it figures out the converter transformer is in charging state. During normal operation ~ the lock function is not in effect. In this way, no maloperation of zero-sequence over-current protection will occur during charging. Furthermore, the reliability of zero-sequence over-current protection is ensured in case of a grounding fault under normal conditions. Finally, fault playback through the fault oscillograph verifies the correctness of this scheme.
作者 冯国东
出处 《电气自动化》 2016年第6期5-7,共3页 Electrical Automation
关键词 直流输电 换流变压器 零序过流保护 二次谐波闭锁 空充标志状态 故障回放 HVDC converter transformer zero-sequence over-current protection second harmonic lock charging mark state fault playback
  • 相关文献

参考文献7

二级参考文献37

  • 1钟胜,郭相国,田昕,李泰军.哈密至郑州特高压直流对受端电网影响分析[J].中国电力,2012,45(11):47-51. 被引量:18
  • 2关洪浩,张锋,孙谊媊,姚秀萍.哈郑直流工程投运初期对新疆电网影响分析[J].中国电力,2012,45(12):48-51. 被引量:20
  • 3宋红涛,胡晓静,王红青,张广朴,王海亮,朱艳娜.高压直流输电系统中交流滤波器连线保护[J].中国电力,2012,45(3):7-10. 被引量:5
  • 4赵畹君.高压直流输电工程技术[M].北京:中国电力出版社,1999.
  • 5中华人民共和国国家标准.GB/T 14285-2006.继电保护和安全自动装置技术规程[S].北京:中华人民共和国国家标准委员会,2006.
  • 6中华人民共和国电力行业标准.DL/T 559-2007 220 kV-750 kV电网继电保护装置运行整定规程[S].北京:中华人民共和国国家发展和改革委员会,2007.
  • 7DL/T559--94220kV-500kV电网继电保护装置运行整定规程[S].北京:中华人民共和国电力工业部,1995.
  • 8水利电力部西北电力设计院.电力工程电气设计手册(电气一次部分)[S].北京:中国电力出版社,1989.
  • 9能源部西北电力设计院.电力工程电气设计手册(电气一次部分)[S].北京:中国电力出版社,1991.
  • 10电力工业部西北电力设计院.电力工程电气设备手册(电气二次部分)[S].北京:中国电力出版社,1996.

共引文献29

同被引文献14

引证文献1

二级引证文献16

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部