新型一体化通信单管塔机房的自然通风设计 被引量:1

Thenatural ventilation design for the equipment room of the new intergration communition monopole
下载PDF
导出
摘要 本文在分析通信机房自然通风影响因素的基础上,结合新型一体化通信单管塔的结构特点,利用烟囱效应原理,对机房进行自然通风设计。利用流体有限元软件FLUENT对通信机房内流场进行仿真分析,得出合理的设置和布局,给出最佳通风方案。通信机房自然通风测试结果表明,这一方式有效降低机房内温度,减少空调运行时间,在满足通信设备的散热需要的同时,达到节能减排的效果。对通信基站的建设与维护有指导意义。 In this paper,a natural ventilation design for the equipment room is provided by using the stack effect principle.The factors affecting the natural ventilation in the communication rom are analyzed with utilizing the characteristics of the new integration communication monopole structural.The flow field in the communication room is analyzed by using fluid finite element software FLUENT.The reasonable arrangement and layout are obtained to present a better ventilation scheme.The results show that the temperature in the room is obviously reduced,and the work time of the air conditioner is reduced effectively through testing the natural ventilation in the communication room.This design reduces the energy emission in the context of the normal work condition of the communication equipment.It is instructive for the construction and maintenance of the communication base station.
作者 辛春雷 芦娜
机构地区 北京邮电大学
出处 《制冷与空调》 2016年第11期91-100,共10页 Refrigeration and Air-Conditioning
关键词 通信机房 自然通风 节能 有限元 communition equipment room natural ventilation energy conservation finite element
  • 相关文献

参考文献1

二级参考文献10

  • 1王金.3G网络拒绝重复建设[N].通信产业报,2006-04-20.
  • 2R. Sharma, C. Bash, C. Patel, M. Beitelmal, Experimental investigation of design and performance of data centers, in: Themlomechanical Phenomena in Electronic Systems - Proceedings of the Intersociety Conference- Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, 2004, vol. 1, pp. 579- 585.
  • 3A. Shah, V. Carey, C. Bash, C. Patel, Energy analysis of data center thermal management systems, J. Heat Transfer, 2008, in press.
  • 4A. Shah, V. Carey, C. Bash, C. Patel, An energy- based figure of merit for electronic packages, J. Electron. Packag 128 (4) (2006)360- 369.
  • 5C.D. Patel, R. Shamla, C.E. Bash,A. Beitelmal, Thermal considerations in cooling large scale high compute density data centers, in: Proceedings of 2002 Inter Society Conference on Thermal Phenomena, 2002.
  • 6S. Kang, R.R. Schmidt, K.M. Kelkar, A. Radmehr, S.V. Patankar, A methodology for the design of perforated tiles in raised floor data centers using computational flow analysis, IEEE Transactions on Computer and Packaging Technologies 24 (2) (2001) 177- 183.
  • 7K. Karki, S. Patankar, A. Radmehr, Techniques for controlling airflow distribution in raised - floor data centers, Adv. Electron. Packag. 2 (2003) 621- 628.
  • 8R. Schmidt, E. Cruz, Cluster of high powered racks within a raised floor computer data center: effect of perforated tile flow distribution on rack inlet air temperatures, J. Electron. Packag., Trans. ASME, Therm. Manag. Electron. Syst. : Four Decades of Progress, December 126(4) (2004)510-518.
  • 9S. Shrivastava, B. Sammakia. R. Schmidt, M. Iyengar, Comparative analysis of different data center airflow management configurations, in: Proceedings of the International Electronic Packaging Technical Conference and Exhibition, San Francisco, CA, 2005.
  • 10K. Karki, S. Patankar, Airflow distribution through perforated tiles in raised - floor data centers, Build. Environ. 41 (2006) 734 - 744.

共引文献19

同被引文献5

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部