摘要
本文以中国移动海南分公司通信基站空调器应用节能增效的极化冷冻机油添加剂(PROA)技术为研究对象,分别分析了不同使用年限、不同环境工况下基站空调用电量的变化规律,提出了横向对比与纵向对比相结合的分析与测试方法,结果发现日最高温度波动在4℃以内,基站的用电量波动范围较小,在0.7%以内。此方法可用于快速测定某区域的节能改造效果评估。
In this paper,the polarized refrigerating machine oil additive( PROA) technology of air-conditioners in communication base stations of Hainan Branch of China Mobile is used to study the change of air-conditioning power consumption in different base stations under different service life and environment conditions. The results show that the daily maximum temperature fluctuation is within 4℃,and the fluctuation range of the power consumption of the base station is small,which is less than 0. 7%. This method can be used to quickly determine the energy saving effect of certain region.
出处
《黑龙江科学》
2016年第22期9-11,共3页
Heilongjiang Science
关键词
基站空调
节能改造
节能测试
Base station air conditioning
Energy saving reconstruction
Energy saving test