期刊文献+

虚拟惯量控制对提高电网一次调频稳定性的影响

Effect of Virtual Inertia Control on the Stability of Primary Frequency Regulation
下载PDF
导出
摘要 大规模风能通过输电线路接入交流系统之后,会使得电网系统惯量逐渐减小,导致系统阻止频率突变的能力下降;同时大容量负荷的切换,也会使电网频率大幅度振荡。为了研究证实虚拟惯量控制对稳定电网频率的支持作用,建立了110 k V直流输电系统仿真模型,利用直流输电电容仿效出虚拟惯量常数加入控制系统中,从而改变电网惯性,改善频率抗干扰能力。仿真结果表明,采用虚拟惯量控制后,在系统功率变化时,调频回路立即动作,响应时间不到0.2 s,畸变幅值远远小于调频要求的1%,增强了一次调频抗干扰能力。 After large-scale wind power connecting to AC system through transmission lines, the inertia of grid system will gradually decrease, and the effect of the system on keeping frequency from sudden change may reduce. Furthermore, the switch with large -capacity load will cause great oscillation of the power system frequency. In order to research and prove the support effect of virtual inertia control on stable grid frequency, it constructed a digital simulation model of 110 kV HVDC system, and utilized DC transmission capacitance to imitate virtual inertia and then put it into control system, thus the grid inertia was changed and the anti-interference ability of frequency was improved. Simulation results indicate that with the virtual inertia control, as the system power changing, the frequency modulation circuit immediately responds, the response time is less than 0.2 s and distortion amplitude is far less than 1%, thus it enhances the anti-jamming capability of primary frequency regulation.
作者 杨亚枢
出处 《大功率变流技术》 2016年第6期52-54,共3页 HIGH POWER CONVERTER TECHNOLOGY
关键词 机械惯量 电网 一次调频 虚拟惯性 风力发电 mechanical inertia power grid primary frequency regulation virtual inertia wind power generation
  • 相关文献

参考文献4

二级参考文献36

  • 1成建鹏,毛承雄,范澍,王丹.电子电力变压器原理和仿真研究[J].电力自动化设备,2004,24(12):23-25. 被引量:16
  • 2尹峰.CCS参与的火电机组一次调频能力试验研究[J].中国电力,2005,38(3):74-77. 被引量:28
  • 3黄宗君,李兴源,晁剑,康鹏.贵阳南部电网“7·7”事故的仿真反演和分析[J].电力系统自动化,2007,31(9):95-100. 被引量:51
  • 4毛承雄,王丹,范澍,等.电力电子变压器[M].北京:中国电力出版社,2010:16-18.
  • 5M. Kayikci and J. V. Milanovic. Dynamic contribution of DFIG--based wind plants to system frequency disturbances [J]. IEEE Trans. Power Syst,2011,24(2):859~867.
  • 6J. F. Conroy and R. Watson, "Frequency response capability of full converter wind turbine generators in comparison to conven- tional generation" [J]. IEEE Trans. Power Syst. 2008,23(2) :649~656.
  • 7M. Zhixin, F. Lingling, D. Osborn, and S. Yuvarajan, "Wind farms with HVdc delivery in inertial response and primary frequency control[J]. IEEE Trans. Energy Convers. , 2010,25(4) :1171~1178.
  • 8Jiebei Zhu, Camplell D. Booth. Inertia Emu- lation Control Strategy for VSC- HVDC Transmission Systems [J]. IEEE Trans,Power Syst. ,2012,28(2) : 1277~1286.
  • 9J. Zhu and C. Booth, "Future multi--termi- nal HVDC transmission systems using volt- age source converters" [J].in Proc. Int. Univ. Power Eng. Conf. , Cardiff, U. K. , 2010, (9) :1~6.
  • 10J. F. Conroy and R. Watson. Frequency re- sponse capability of full converter wind tur- bine generators in comparison to convention- al generation[J]. IEEE Trans. Power Syst. 2010,23(2) :649~656.

共引文献80

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部