摘要
简要介绍集装箱式数据中心吊顶式空调的结构和系统原理,将其与普通机房空调进行测试对比,测试结果表明,吊顶式空调的能效比远高于普通机房空调,显热制冷量也高于普通机房空调,比普通机房空调更节能。
The structure and system principle of ceiling air-conditioning for container data center are introduced, and it is compared with the common computer room air-condi- tioning by test. The test results show that the EER of the ceiling air-conditioning is far higher than that of common computer room air-conditioning, and the cooling capacity of sensible heat as well. So the ceiling air-conditioning is more energy efficient than the com- mon computer room air-conditioning.
出处
《制冷与空调》
2016年第12期12-14,共3页
Refrigeration and Air-Conditioning
关键词
集装箱式数据中心
吊顶式空调
能效比
container data center
ceiling air-conditioning
energy efficiency ratio