期刊文献+

采用微通道冷凝器的制冷机组启动高压跳停的解决方法

Solutions of high-pressure trip at start-up of refrigeration unit using MCHE condenser
下载PDF
导出
摘要 针对采用微通道冷凝器的制冷机组在低室温高环温工况下启动时容易出现高压跳停的问题,通过对微通道换热器与传统翅片管式换热器内容积差异的分析,从改善系统设计方面入手,提出减少制冷剂充注量,使制冷剂快速回到蒸发器继续循环,以及加大冷凝器侧容积的方法,为采用微通道冷凝器的制冷机组的设计提供参考。 According to the issue of high-pressure trip at the start-up in low indoor temperature and high ambient temperature condition for refrigeration unit using micro- channel heat exchanger (MCHE) as the condenser, through analyzing and comparing the internal volume difference between MCHE and the finned-tube heat exchanger, some solu- tions are proposed to improve the system design, such as decreasing the system's refriger- ant charge, accelerating refrigerant to cycle back to evaporator and increasing the internal volume on the condenser side, which provide a good reference for the design of refrigera- tion unit using MCHE condenser.
出处 《制冷与空调》 2016年第12期22-25,共4页 Refrigeration and Air-Conditioning
关键词 微通道换热器 翅片管式换热器 高压跳停 micro-channel heat exchanger (MCHE) finned-tube heat exchanger high-pressure trip
  • 相关文献

参考文献1

二级参考文献5

  • 1谢旭明,石文星.制冷系统中制冷剂分布特性的研究现状[J].制冷与空调,2004,4(6):1-4. 被引量:14
  • 2Mulroy W J,Didion D A.Refrigerant migration in a split-unit air conditioner[J].ASHRAE Transactions,1985,91(1):193-206.
  • 3Tanaka N,Lkeuchi M,Yamanaka G.Experimental study of the dynamic characteristics of a heat pump[J].ASHRAE Transactions,l982,88(2):323-331.
  • 4Janssen M J P,Wit J A,Kuijpers L J M.Cycling losses in domestic appliances:an experimental and theoretical analysis[J].International Journal of Refrigeration,1992,15(3):152-158.
  • 5姬长发,刘顺波.变频空调器中工质分布实验研究[J].流体机械,2002,30(1):49-50. 被引量:9

共引文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部