导出
摘要 目的了解浙江省某市空调冷却系统中的军团菌污染状况,并分析与军团菌污染相关的环境因素,为预防和控制军团菌病提供科学依据。方法随机选取浙江省某市的10家大型公共场所的中央空调作为检测对象,检测项目包括空调的使用年限、空调的清洁与卫生管理状况、冷却水的温度、p H和浊度。结果经检测得出真菌总数只有2家不合格,细菌总数有1家不合格。冷却水的水温为24.3℃~31.8℃,p H值为7.40~7.91。浊度为3 NTU^10 NTU,军团菌的检出率高达70%。检测的项目中仅有冷却水的浊度与军团菌的检出率有显著相关性。结论空调冷却水的浊度可能是影响军团菌生长的重要因素,加强空调冷却水卫生管理有利于预防军团菌病。 Objective To investigate the Legionella contamination of air-conditioning cooling system in a city in Zhejiang,and to analyze the relevant environmental factors,so as to provide scientific evidence for the prevention of Legionella disease. Methods Chose randomly centralized air-conditioning of 10 large public spaces in a city of Zhejiang,and test items include air conditioning service age,clean and hygienic condition of air conditioning,cooling water temperature,p H and turbidity. Results The total count of Fungi did not meet standard in 2 places,so did the count of bacteria in 1 place. The temperature of cooling water was within 24. 3℃-31. 8℃,p H was within 7. 40-7. 91. Turbidity was in 3 NTU-10 NTU,and the detection rate of Legionella was up to 70%. There was a significant correlation between the turbidity of cooling water and the detection rate of corps bacteria.Conclusion Turbidity of cooling water is a critical factor that may influence the growth and reproduction of Legionella pneumophila. Strengthening the management of cooling water is of great public health significance in preventing Legionella disease.
出处 《中国卫生检验杂志》 CAS 2016年第24期3605-3607,共3页 Chinese Journal of Health Laboratory Technology
基金 浙江省新苗人才计划资助项目(2016R410044)
关键词 公共场所 空调冷却系统 军团菌 影响因素 Public places Air conditioning cooling system Legionella bacteria Influence factors
  • 相关文献

参考文献11

二级参考文献98

共引文献55

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部