500kV失灵保护误动分析与反措 被引量:1

Analysis of 500kV Failure Portecion Misoperation and Its Anti Accident Measures
下载PDF
导出
摘要 阐述了一起500kV失灵保护误动事故,其误动原因是母线保护失灵回路光耦开入回路设计不完善,动作电压不满足55%~70%额定直流电压要求,当光耦正端接地时,造成光耦开入回路误导通而母线失灵保护误动作出口。根据国家电网公司继电保护反事故措施要求,对母线保护开入回路插件进行更换,以满足动作电压要求。 This paper describes a 500kV failure portccion misoperation accident, the reason of misoperation is that the design of busbar protection failure loop' s optocoupler open circuit is not complete, its action voltage could not satisfy 55%-70% DC voltage range. Optocoupler' s positive is grounded, which leads to circuit' s conduction and busbar failure protection trip. According to state grid corporation' s anti accident measurement, open circuit is replaced, which satisfying action voltage.
作者 惠杰 刘妮娜 冯迎春 HUI Jie LIU Ni-na FENG Ying-chun(Shandong Electric Power Maintenance Company, Ji ' nan 250018,Chirm ShandongElectricPowerlnduslryBoiler&PressureVessellnspeetionCentreCo. Ltd.,Ji 'nan 250002,China)
出处 《工程建设与设计》 2017年第2期64-65,共2页 Construction & Design for Engineering
关键词 失灵保护 光耦 动作电压 failure protection optocoupler action voltage