数据中心制冷系统冷源选择及能效分析 被引量:12

Cold Source Selection and Efficiency Analysis of Data Center Cooling Systems
原文传递
导出
摘要 本文针对我国不同气候区的气候特点,以某中等规模数据中心为例,对风冷式直接蒸发系统和水冷式冷水机组系统两种常用的数据中心制冷系统进行了能效分析,量化给出了季节性和区域性气候差异对数据中心制冷系统的能效影响,分析了风冷式和水冷式系统在不同气候区的应用优势。对一种将热管循环与蒸气压缩制冷循环相结合的复合型自然冷源系统进行了运行测试,计算给出了不同气候区自然冷源的可用时间和节能潜力,分析结果可用于数据中心选址以及其制冷系统的优化设计。 This paper analyzed the energy efficiency of two commonly used cooling systems (including the air-cooled type and the water-cooled type) in data centers according the climatic characteristics of different climate zones based on the energy consumption measuring results of a medium size data center. The results revealed the influence of the seasonal and regional climate differences on the performance of the data center cooling systems and also showed the application advantages of the air-cooled and water-cooled systems. An operation test on a free cooling system combining the heat pipe cycle and the vapor compression cycle was conducted. The results concluded the available time and energy saving potential of the combined system in different climate zones, which can be used in the site selection of data centers and the optimization of the data center cooling systems.
出处 《工程热物理学报》 EI CAS CSCD 北大核心 2017年第2期326-332,共7页 Journal of Engineering Thermophysics
基金 科技部国家重点研发计划(No.2016YFB0601601) 国家自然科学基金(No.51321002,No.51376097)
关键词 数据中心 制冷系统 自然冷源 气候类型 能效分析 data center cooling system free cooling climate type efficiency analysis
  • 相关文献

参考文献1

二级参考文献3

  • 1中国标准化研究院.GB19577-2004冷水机组能效限定值及能源效率等级[S].北京:中国建筑工业出版社,2004.
  • 2中国标准化研究院.GB 19576—2004单元式空气调节机能效限定值及能源效率等级[S].北京:中国标准出版社,2004.
  • 3艾默生网络能源有限公司,合肥通用机械研究院,广东吉荣有限公司.GB19413--2003计算机和数据处理机房用单元式空气调节机[S].北京:中国标准出版社,2011.

共引文献9

同被引文献124

引证文献12

二级引证文献50

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部