异程管网热湿负荷分配次优解群及适应性 被引量:2

Suboptimal group and adaptability analysis of thermal-humidity load distribution of drect-return chilled water system
下载PDF
导出
摘要 提出了一种基于次优解群统计分析的异程管网热湿负荷分配方法,采用变步长+随机走步的寻优计算方法,获得空调季不同负荷率下热湿负荷再分配的次优解群,分析次优解群的随机行为和统计规律,以此探索复杂变量约束下的冷冻水系统负荷分配的优化控制策略及其适应性。根据计算结果,在40%、60%、80%、100%这4种负荷率下末端人数次优解重叠率最高达到24%。研究表明,次优解群随机行为与管网热湿负荷分配策略存在相关性,离冷源侧越近,末端人数次优解重叠率越高,分配策略的负荷适应性越好,其权重越大。 A way of thermal-humidity load distribution of direct-return chilled water system based on the suboptimal group was proposed.And the sub-optimization method of variable step size combined with the random walking was adopted.After obtaining suboptimal group of thermal-humidity load distribution in different load rate in the air-conditioning season,it would analyze random behavior and statistical law of the suboptimal group.So that the optimal control strategy and adaptability of chilled water system could be explored in constraint of complex variable.The results showed that the most overlapped ratio of the suboptimal solution of terminal numbers reached 24 percent under the four load rate,for example,40%,60%,80%,100%.A correlation between random behavior of suboptimal group and strategy of heat and moisture load distribution for chilled water system was found,and the optimal solution of terminal numbersnearer cold sources had the higher overlapped ratio,better adaptability of distribution strategy,larger weight.
出处 《土木建筑与环境工程》 CSCD 北大核心 2017年第1期51-59,共9页 Journal of Civil,Architectural & Environment Engineering
基金 国家科技支撑计划(2012BAJ06B06) 广东省自然科学基金(2015A030310303) 中央高校基本科研业务费专项资金(B6150170)~~
关键词 冷冻水系统 异程布置 热湿负荷重构 适应性 chilled water system direct-return layout thermal-humidity load reconstruction adaptability
  • 相关文献

参考文献11

二级参考文献136

共引文献478

同被引文献19

引证文献2

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部