期刊文献+

500kV典型输电线路铁塔附近电场测量与仿真分析 被引量:6

Measurement and Simulation Analysis on Electric Field Near 500 kV Typical Power Transmission Tower
原文传递
导出
摘要 实地测量了三种典型500 kV铁塔附近离地1.5 m高的工频电场。搭建了三维铁塔模型,基于有限元法仿真计算了三种塔型附近工频电场分布,分析了测量值与计算值的差别及影响因素,并结合实际工程求解了两种典型的等电位作业路径上的电场分布。研究结果表明:铁塔附近地面上工频电场实测值均满足环评要求;铁塔对附近地面的电场具有一定屏蔽作用;采用该方法计算的结果与测量值一致,可以推广到构造更为复杂的输电线路电场计算,并为线路设计提供一定的理论依据;两种等电位作业路径的电场分布差别不大,实际路径的选取应主要考虑到带电作业危险率和所需最小安全距离这两大因素。 The power frequency electric field near three typical 500 kV power transmission tower1.5 m above ground is measured. Based on finite element method (FEM), three-dimensionaltransmission tower calculation models are established and the electric field distribution of powerfrequency electric field near the three different type towers are simulated and calculated. Thedifferences between measurements and calculated results, and the influence factor are both analyzed.The electric field distribution along two typical equal potential working route are also researchedcombined with practical engineering. Research results show that electric field measurements nearby thetower meet EIA requirements; the tower has a certain screening effect on its electric field nearby; theresults calculated by method presented above matches well with the field measurements, can bepromoted to tower with more complex structure, and provide theoretical basis for the design of EHVtransmission lines; the electric field distribution difference between two typical equal potential workingroute is slight, thus selection of actual routes should mainly take dangerous rate for equal potentialworking and required minimum safe distance into account.
出处 《电瓷避雷器》 CAS 北大核心 2017年第1期30-36,共7页 Insulators and Surge Arresters
关键词 典型铁塔模型 工频电场测量 有限元法 等电位作业 typical tower model power electric field measurement finite element method (FEM) equal potential working
  • 相关文献

参考文献13

二级参考文献135

共引文献277

同被引文献107

引证文献6

二级引证文献31

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部